Applications
When a constant monitoring system, such as a PT or personal computer appli-
constantly
cation, is connected to the CPU Unit's RS-232C port, an RS-232C/RS-422
connected to
Adapter can be used to connect to both the active and standby CS1D CPU
RS-232C port
Units.
in Duplex
Set the standby CPU Unit's RS-232C port setting in the PLC Setup so that it
CPU Systems
cannot be used independently.
Restrictions
When writing to a Memory Card, the same data is written to not only the Memory
on Memory
Card mounted in the active CPU Unit, but also to the one mounted in the
Card func-
standby CPU Unit.
tions
Note In the PLC Setup, duplex operation must be enabled for Memory Cards.
(Duplex CPU
Note No processing is executed during duplex initialization to match the data
Systems only)
on the Memory Cards mounted in the active and standby CPU Units even
if the data is not the same. Therefore, before enabling duplex operation
for Memory Cards, make sure that the contents are the same for both of
the Memory Cards.
Note When EM File Memory is set for duplex operation, processing is exe-
cuted to match the contents of EM File Memory in both CPU Units. It is
not necessary to enable duplex operation for Memory Cards in the PLC
Setup.
Specifications
@
CX-Programmer Ver. 3.
@@
tem uses the CS1D-CPU
device type. This version does not support Single CPU
Systems.
CX-Programmer Ver. 4.0 or higher: The Duplex CPU Sys-
@@
tem uses the CS1D-CPU
"CS1H-H" as the device type. The Single CPU System
@@
uses the CS1D-CPU
S, so select "CS1D-S" as the
device type.
Cable connection: Connect to the peripheral port or RS-
232C port of the active CPU Unit.
Note If a CX-Programmer is connected to the standby
CPU Unit in a Duplex CPU System, write process-
ing from the CX-Programmer cannot be executed.
Cable connection: Connect to peripheral port of active
CPU Unit.
If a Programming Console is connected to the standby
CPU Unit, write processing from the Programming Con-
sole cannot be executed.
or lower: The Duplex CPU Sys-
H, so select "CS1H-H" as the
H, so select "CS1D-H" or
Section 2-1
Reference
2-6-2 Precautions
when Connecting Pro-
gramming Devices to
Duplex CPU Systems
6-2-11 CPU Duplex Tab
Page
Appendix F Connect-
ing to the RS-232C
Port on the CPU Unit
2-5-1 File Memory
Functions in Duplex
CPU Systems