Omron CS1D DUPLEX SYSTEM - 10-2009 Operation Manual page 523

Cs1d duplex system
Table of Contents

Advertisement

Specifications of Basic I/O Units and High-density I/O Units
CS1W-MD261 24-V DC Input/Transistor Output Unit (32/32 Points, Sinking)
Output section (CN1)
Rated Voltage
Operating Load Voltage
Range
Maximum Load Current
Maximum Inrush Cur-
rent
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
No. of Circuits
Fuses
External Power Supply
Insulation Resistance
Dielectric Strength
Internal Current Con-
sumption
Weight
Accessories
12 to 24 V DC
10.2 to 26.4 V DC
0.3 A/point, 1.6 A/common,
3.2 A/Unit
3.0 A/point, 10 ms max.
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
32 (16 points/common, 2 circuits) OFF Response Time
None
10.2 to 26.4 V DC, 30 mA min.
20 M between the external terminals and the GR terminal (100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage cur-
rent of 10 mA max.
5 V DC 270 mA max.
260 g max.
Two connectors for external wiring (soldered)
Input section (CN2)
Rated Input Voltage
24 V DC
Allowable Input Voltage
20.4 to 26.4 V DC
Range
Input Impedance
3.9 k
Input Current
6 mA typical (at 24 V DC)
ON Voltage/ON Current
15.4 V DC min./3 mA min.
OFF Voltage/OFF Cur-
5 V DC max./1 mA max.
rent
ON Response Time
8.0 ms max. (Can be set to
between 0 and 32 in the PLC
Setup.) (See note.)
8.0 ms max. (Can be set to
between 0 and 32 in the PLC
Setup.) (See note.)
No. of Circuits
32 (16 points/common, 2 circuits)
Number of Simulta-
70% (11 points/common)
neously ON Points
(at 24 V DC)