Auxiliary Area Allocations
Address
Name
Words
Bits
A406
All
PLC Setup
Error
Location
A407
A40700
Too Many
to
I/O Points,
A40712
Details
A40713
Too Many
to
I/O Points,
A40715
Cause
A408
A40800
Basic I/O
to
Unit Error,
A40807
Slot Num-
ber
A40808
Basic I/O
to
Unit Error,
A40815
Rack
Number
A409
A40900
Expan-
to
sion I/O
A40907
Rack
Number
Duplica-
tion Flags
A410
A41000
CPU Bus
to
Unit Num-
A41015
ber Dupli-
cation
Flags
532
Function
When there is a setting error in the
PLC Setup, the location of that error
is written to A406 in 4-digit hexadec-
imal. The location is given as the
address displayed on a Program-
ming Console.
The CPU Unit will continue operat-
ing and the ERR/ALM indicator on
the front of the CPU Unit will flash.
(A406 will be cleared when the
cause of the error is eliminated.)
When there are too many I/O, CPU
Unit operation will stop, the ERR/
ALM indicator on the front of the
CPU Unit will light, and one of the
following values will be stored here.
The total number of I/O points will be
written here if the capacity of the
CPU Unit is exceeded.
The number of Racks will be written
here when the number of Expansion
I/O Racks exceeds the maximum.
Number of interrupt input points
when there are more than 32 (Single
CPU Systems only)
(These bits will be cleared when the
error is cleared.)
The 3-digit binary value of these bits
indicates the cause of the Too Many
I/O Points Error and shows the
meaning of the value written to bits
A40700 to A40712.
(These bits will be cleared when the
error is cleared.)
When an error has occurred in a
Basic I/O Unit, A40212 will be
turned ON and the slot number
where the error occurred will be writ-
ten here in binary.
(These bits will be cleared when the
error is cleared.)
When an error has occurred in a
Basic I/O Unit, A40212 will be
turned ON and the Rack number
where the error occurred will be writ-
ten here in binary.
The CPU Unit will continue operat-
ing and the ERR/ALM indicator on
the front of the CPU Unit will flash.
(These bits will be cleared when the
error is cleared.)
The corresponding flag will be
turned ON when an Expansion I/O
Rack's starting word address was
set from a Programming Device and
two Racks have overlapping word
allocations or a Rack's starting
address exceeds CIO 0901. Bits 00
to 07 correspond to Racks 0 to 7.
(The corresponding flag will be
cleared when the error is cleared.)
The Duplication Error Flag (A40113)
and the corresponding flag in A410
will be turned ON when an CPU Bus
Unit's unit number has been dupli-
cated. Bits 00 to 15 correspond to
unit numbers 0 to F.
CPU Unit operation will stop and the
ERR/ALM indicator on the front of
the CPU Unit will light.
Settings
Status
after
mode
change
0000 to 01FF
Cleared
hex
0000 to 1FFF
Cleared
hex
000: Too many
Cleared
I/O total
001: Too many
interrupt input
points
101: Too many
Racks
00 to 09 hex
Cleared
(Slots 0 to 9)
00 to 07 hex
Cleared
(Racks 0 to 7)
ON: Error
Cleared
OFF: No error
ON: Duplication
Cleared
detected
OFF: No dupli-
cation
Appendix B
Status at
Timing
Related
startup
flags,
settings
Cleared
When
A40210
error
occurs
Cleared
When
A40111,
error
A40713
occurs
to
A40715
Cleared
When
---
error
occurs
Cleared
---
A40212
Cleared
---
A40212
Cleared
---
---
Cleared
---
A40113