Specific PLC Setup Settings
Enable Watch Cycle Time Setting
Address in
Programming
Console
Word
Bit(s)
209
15
0: Default
1: Bits 0 to 14
Default: 0
Cycle Time (Minimum Cycle Time
Address in
Programming
Console
Word
Bit(s)
208
0 to 15
0001 to 7D00 hex: 1
to 32,000 ms
(1-ms units)
Default: 0000 hex
(No minimum)
Schedule Interrupt Interval (Single CPU Systems Only)
Address in
Programming
Console
Word
Bit(s)
195
0 to 3
0 hex: 10 ms
1 hex: 1.0 ms
Default: 0 hex
Settings
Set to 1 to enable the Watch Cycle Time
Setting in bits 0 to 14. Leave this setting at 0
for a maximum cycle time of 1 s.
)
Settings
Set to 0001 to 7D00 to specify a minimum
cycle time (in parallel processing mode, the
cycle time for instruction execution, see
note). If the cycle time is less than this set-
ting, it will be extended until this time
passes. Leave this setting at 0000 for a vari-
able cycle time. (Can't be changed during
operation.)
Note Single CPU Systems only.
Settings
Sets the time interval for the scheduled
interrupt task.
Note This setting cannot be used with Duplex CPU Systems.
Function
Function
Function
Section 6-2
Related
New set-
flags and
ting's effec-
words
tiveness
A40108
At the start of
(Cycle Time
operation
Overrun Flag)
(Can't be
changed dur-
ing opera-
tion.)
Related
New set-
flags and
ting's effec-
words
tiveness
---
At the start of
operation
(Can't be
changed dur-
ing opera-
tion.)
Related
New set-
flags and
ting's effec-
words
tiveness
---
Takes effect
at the start of
operation.
(Can't be
changed dur-
ing opera-
tion.)
197