Specifications of Basic I/O Units and High-density I/O Units
CS1W-OD212 Transistor Output Unit (16 Points, Sourcing)
Rated Voltage
Operating Load Voltage
Range
Maximum Load Current
Leakage Current
Residual Voltage
ON Response Time
OFF Response Time
Load Short-circuit Prevention
Insulation Resistance
Dielectric Strength
No. of Circuits
Internal Current Consumption 5 V DC 170 mA max.
External Power Supply
Weight
Circuit Configuration
Terminal Connections
Note Terminal numbers A0 to A9 and B0 to B9 are used in this manual, but they are not printed on the Unit.
24 V DC
20.4 to 26.4 V DC
0.5 A/point, 2.5 A/common, 5.0 A/Unit
0.1 mA max.
1.5 V max.
0.5 ms max.
1.0 ms max.
Detection current: 0.7 to 2.5 A
Automatic restart after error clearance. (Refer to page 499.)
20 M between the external terminals and the GR terminal (100 V DC)
1,000 V AC between the external terminals and the GR terminal for 1 minute at a leakage
current of 10 mA max.
16 (8 points/common, 2 circuits)
20.4 to 26.4 V DC, 40 mA max.
270 g max.
Output indicator
ERR indicator
When overcurrent is detected, the ERR indicator will light, and the corresponding flag in
the Basic I/O Unit Information Area (A050 to A089) will turn ON.
0
A0
L
1
B0
L
2
A1
L
3
B1
L
4
A2
L
5
B2
L
6
A3
L
7
B3
L
0V
A4
COM0(+V)
B4
8
A5
L
9
B5
L
10
A6
L
11
B6
L
12
A7
L
13
B7
L
14
A8
L
15
B8
L
0V
A9
COM1(+V)
B9
When wiring, pay careful attention to the polarity of the external power supply. The load
may operate if the polarity is reversed.
COM0 (+V)
OUT00
to
OUT07
0 V
COM1 (+V)
OUT08
to
OUT15
0 V
24 VDC
24 VDC