5.4 Restoring the factory settings

4. Switch on the motor.
The inverter starts the motor data identification. This measurement can take several
minutes.
Depending on the setting, after motor data identification has been completed, the inverter
switches off the motor - or it accelerates it to the currently set setpoint.
5. If required, switch off the motor.
6. Relinquish the master control after the motor data identification.
7. Press button
You have completed the motor data identification.
5.4
Restoring the factory settings
There are cases where something goes wrong when commissioning a drive system e.g.:
● The line voltage was interrupted during commissioning and you were not able to complete
commissioning.
● You got confused during the commissioning and you can no longer understand the
individual settings that you made.
● You do not know whether the inverter was already operational.
In cases such as these, reset the inverter to the factory setting.
Restoring the factory settings when the safety functions are enabled
If you are using the integrated safety functions of the inverter, e.g. "Safe Torque Off", you
must reset the safety functions separately from the remaining inverter settings.
The settings of the safety functions are protected by a password.
Settings that are not changed when restoring the factory setting
The communication settings and the settings of the motor standard (IEC/NEMA) are kept
when restoring the factory setting.
5.4.1

Resetting the safety functions to the factory setting

Procedure with STARTER
To reset the safety function settings to the factory setting without changing the standard
settings, proceed as follows:
1. Go online.
2. Open the screen form of the safety functions.
124
(RAM to ROM).
Operating Instructions, 06/2016, FW V4.7.6, A5E31298649B AG