2.2.4.4 BACNET interface

The integration of HITACHI systems into a BACNET installation can be carried out by using a double gateway system:
HITACHI MODBUS gateway: HC-A(8/64)MB, PSC-A160WEB1 or CSNET Manager with HC-A64NET which provide
HLINK data into a MODBUS protocol.
Standard MODBUS-BACNET gateway available in the market which transfers MODBUS data into BACNET data.
There are wide several solutions available in the market which should allow the transfer of MODBUS collected data by
HITACHI gateways into BACNET data. Anyway, HITACHI recommends the solution offered by Intesis Software company
that offers 6 possible devices available for such applications, which are different in terms of:
No. of points (parameters) available: 100, 500, 1000.
Type of MODBUS channel: RTU (only with HC-A(8/64)MB) or TCP (for all the options).
BACNET-MODBUS
GATEWAY
Option 1: Gateway interfaces to MODBUS systems (HC-A(8/64)MB)
Easy integration of HITACHI Air Conditioning installations to MODBUS BMS protocol.
HC-A8MB: max. 8 indoor units.
HC-A64MB: max. 64 indoor units.
Option 2: CSNET WEB hardware interface (PSC-A160WEB1)
This option allows to take advantage of the CSNET WEB functionality.
Option 3: CSNET Manager and its H-LINK gateway (HC-A64NET)
This option allows to take profit of the great CSNET Manager functionality, connecting it to its HC-A64NET gateway.
(*): Using CSNET Manager with other CSNET Managers or with CSNET WEB hardware (PSC-A160WEB1) the maximum
number of controllable indoor units is increased up to 1280 indoor units.
19
19
TCGB0106 rev.0 - 12/2014
OPTION 1
HC-A(8/64)MB
MODBUS
OPTION 2
PSC-A160WEB1
OPTION 3
CSNET MANAGER
(LT/XT)
HC-A64NET
ETHERNET
Up to (8/64)
indoor units
Up to 640 (160x4)
indoor units
Up to 512 (64x8)
indoor units (*)