6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)

Ethernet gateway
You can change the IP and MAC values of your Getaway here by clicking the button Change.

BMS configuration
Modbus Configuration
CSNET WEB allows to configure the BMS system by setting the ID for each indoor unit. This configuration will link the BMS
with the H-LINK.
To open the BMS configuration click on the change button. After clicking the button a dialog will appear and you could start
to set the configuration.
BMS Configuration for Packaged
In this dialogue you can enable the BMS to activate this option, and after this, set in each row the unit information.
-
OU is the outdoor unit number.
-
IU is the indoor unit number.
-
Location is the location field of the unit. This field is only editable from the unit setting tab.
-
ID field is automatically set and is not modifiable.
CSNETWEB automatically assigns an ID for each found unit. You can change this ID on the table.
The ID field can not be repeated, if it will occurs, CSNET WEB will ask you to change the repeated ID.
In case of Packaged, "Auto Set Id" button will be available. This button open a new window when user could automatically
assign the ID to the units. This assignation could be done in two ways:
-
H-LINK I: BMS ID = OU x 16 + IU.
-
H-LINK II: BMS ID is assigned following the order of OU & IU.
442
442
TCGB0106 rev.0 - 12/2014