6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)

DIP switch adjustment
During the installation it must be specified what kind of units are installed.
PSC-A160WEB1 offers a variety of options letting you know its status at all times. These options are only accessible from
the hardware itself.
To activate a function:
1 Remove the four screws in the upper part of the hardware.
2 Locate the "Option" Dip-Switch.
3 Put the pin of the function required into the "ON" position.
4 Put the pin 1 to "ON" to activate the function.
When the dip-switch has been configured, the seven-segment display shows different characters according to the func-
tion established. The values appear as rolling text.
To deactivate the function and return to rest mode:
In the "Option" Dip-Switch put all the pins to "OFF", leaving the pin 1 until last.

Factory dsw setting
OPTION DSW2

DSW2 options setting
The table with all the functions and their description is shown below.
Pins
Function
1
Function selection
Restore the network configu-
2
ration
3
Restore passwords
4
Restore configuration
5
Notification of the IP address
6
Information on units
7
Central Station compatibility
8
Not used
All OFF
Rest
423
423
TCGB0106 rev.0 - 12/2014
MODE DSW6
HLINK DSW7
This pin enables the activation of the functions selected with the other pins.
Restore the IP address Mask and Gateway to the initial values of:
IP: 192.168.0.3
Mask: 255.255.255.0
Gateway: 192.168.0.1
Set the "User" password to "User" and the "Installer" password to "Installer"
Deletes the configuration of the installation and restores the passwords as in the previous
point
Shows the IP address and the PSC-A160WEB1 port.
Shows the number of indoor and outdoor units recognized by PSC-A160WEB1.
It enables the compatibility with central stations.
CSNET WEB software has always priority so if a unit is set as central, Central Station will
not be able to modify the state of the unit. The same happens with Remote Sensor not
configured option.
C A U T I O N
All units should be controlled by a Central Station, otherwise it will appear a communication
alarm.
Internal use, it always must be set as "OFF".
Indicates the type of installation (PA: Packaged). If there is an alarm it shows the alarm
code and the units with this alarm.