8 Control support devices
PSC-A1T

Setting timer pause
<Function>
This function is for cancelling the running schedule.
During the timer pause setting, the ON time setting is invalid and the schedule operation is cancelled.
This function is used in case that there are any long-term holidays.
Press the "HOLIDAY" switch for 3 seconds during the monitor mode.
The mode of the control timer is changed to the timer pause mode, the "HOLI" indication is flickered.
The diagram on the right shows the selection of the timer pause mode.
C A U T I O N
The timer pause function is not available for the day when the setting is performed. This function is available from the next day
and continued until the cancellation of this setting. In this mode, the unit operation is stopped according to OFF time setting.
During the setting mode, the timer pause setting is not available by depressing "HOLIDAY" switch for more than 3 seconds.
During the timer pause mode, the input of only the "HOLIDAY" switch is valid. To input from other switches for setting, the timer
pause mode is required to be cancelled.
When the timer pause mode and the holiday setting day is overlapped, the priority is given to the holiday setting.
Cancellation for Timer Pause Mode.
Press the "HOLIDAY" switch for 3 seconds during the timer pause mode. The control timer is
changed to the monitor mode, the "HOLI" indication turns OFF.
The diagram on the right shows the case of returning to the monitor mode.
N O T E
After cancellation of the timer pause mode, the schedule running is performed by judging ON/OFF time setting.
In the case where the day, when the timer pause mode is cancelled, is set as holiday, the state of "HOLI" indication is changed
from flickering to turning ON.
C A U T I O N
The remote control has a built-in backup battery, making the clock function available for 2 weeks in the event of power failure.
If the power failure should last for more than 2 weeks, the current time will need to be reset.
The "RUN" indicator will switch on at the "ON" time and switch off at the "OFF" time.
If the indoor unit is switched on or off from the control station or remote control used in conjunction with the timer, the "RUN" indica-
tor will not change.
If the "RUN" indicator is flashing, this indicates an abnormal condition on the timer.
Check that the cable connections and DIP switch settings are correct. If the "RUN" indicator continues to flash after the check, con-
tact your dealer or HITACHI supplier.
N O T E
When an on or off order is sent from the timer, it may take around 15 seconds for the order to take effect.
During setting mode, on/off orders cannot be sent to the units.
Once the setting is complete, activate the timer monitor mode. (After remaining in setting mode for 3 minutes, the timer will switch
automatically to monitor mode).
When using the central station timer (PSC-A64S), the settings made through the central station are required.