6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)

Change password
The Change button beside Password setting opens the Change password panel.
To change your password:
-
Enter the installer password. (The default factory password is "Installer").
Enter the new password.
-
-
Repeat the new password to confirm it.
-
Click the "OK" button to validate the changes and return to system configuration window.
N O T E
Only Installer password may be changed for CSNET WEB Server. User password will no longer be used for CSNET WEB Server.

Installation name
The name of the installation is the title of the main window. This lets you identify where CSNET WEB is connected.
To change the name of the installation first enter the name you want and then click on the Change button by the "Installa-
tion Name" line.
This takes you to the main window, where you can see that the title of the main page has changed.

Auto configuration
When the system is started for the first time, it recognizes all the machines connected to H-Link. With time, the air condi-
tioning installation may undergo changes which have certain repercussions on CSNET WEB. If the system detects ma-
chines which have been added after CSNET WEB was installed, or that machines have been removed from the H-Link,
the Auto Configuration function lets you recognize all the machines again.
There are three Auto Configuration options:
Keep All: Only the machines found are added. The other machines in the table of indoor units are kept as they
-
were.
Delete Not Found: If there are machines in the table of indoor units which are not present in the H-Link, CSNET
-
WEB will delete these machines. All the machines which were not present in the table of indoor units but in the
H-Link will be added.
Delete all: All the machines in the table of indoor units will be deleted, and CSNET WEB will again detect all the
-
machines connected to H-Link. Once they are added, you have to remember that the configuration has to be car-
ried out again.