5 Centralised remote controls
PSC-A32MN
<Outdoor Unit Capacity Control>
5 Select the value for Outdoor Unit Capacity.
*
The selected capacity value button is highlighted in yellow.
6 Use the buttons on the right side of the screen in order to schedule outdoor unit capacity control when there is no
external input contact being applied for this purpose.
*
Select "Enable" or "Disable".
*
Tap " " or " " to set the applicable starting time and ending time, in 30 minute steps.
*
When the ending time falls earlier than the starting time, ending time becomes effective on the next day.
For example :
Starting Time 15:00
Ending Time 08:00,
Capacity control starts at 15:00 and ends at 08:00 on the following day.
7 Tap "Register"
8 Select the target of capacity control (Refrigerant system).
*
The buttons of the numbers of refrigerant systems of registered outdoor units are indicated in blue.
*
The buttons of the numbers of refrigerant systems of unregistered outdoor units are indicated in grey. These refriger-
ant systems cannot be selected.
*
Tap the button of a refrigerant system number in order to switch its selection state.
*
Tap "Selec. all refr. syst" to switch the selection state of all refrigerant systems.
*
The selected refrigerant systems are indicated with a check mark.
9 Tap "Setting completed" to confirm the setting contents and return to the External Input/Output Setting screen.