6 Building air conditioning controls
CSNET Manager LT/XT
Power meter
Power Meter tab lets the user configure a TCP-MODBUS power meter for each outdoor unit.
For each power meter device there should be entered the following parameters:
IP Address: LAN address of the power meter.
Power Meter ID: identifier to know which of the power meters is used.
Registers: The Modbus Address and the measurement unit of each of the four variables available on the table should
be configured by the user according to the specific power meter information.
C A U T I O N
Suggested device tested by Hitachi is 7KM PAC3200 by Siemens.
Ensure that your Modbus-TCP power meter register starts at 0. CSNET Manager considers it like this, so if it starts at 1, subtract 1 to
each register address.