7 Gateways for building management systems
HC-A16KNX
DIP switch setting
Name
Function
SW1
Reset KNX PCB
SW2
Reset
SW3
Not available
(TELE)
SW4
Configuration
SW5
Configuration
SW6
Configuration
SW7
Options 2
Options 1
SW8
(Application type)
SW9
Not available
SW10
Not available
SW11
H-LINK DSW
D4, D11
H-LINK
D5
Not used
Units configuration
D6
alarm
D7
Power
D9/D10
Not used
D12
KNX
D13
Operation
640
640
TCGB0106 rev.0 - 12/2014
Factory setting
Reset button. To be used in case of KNX communication has been
–
locked.)
–
Reset button. To be used in case of program has been locked
Factory purposes. Never change it
–
Setting functions
–
Setting functions
–
Setting functions
Configuration as MASTER HC-A16KNX: SW7-1=ON.
Only one HC-A16KNX can be set as a MASTER HC-A16KNX. Setting
by default.
Configuration as SLAVE HC-A16KNX: SW7-1= OFF.
It should be 1 HC-A16KNX configured as MASTER, all the rest of HC-
A16KNX must be configured as SLAVE
All in off (no function)
All in off (no function)
All in off (no function. Do not change)
SW11-1: H-LINK end resistance
SW11-2: Not used
–
H-LINK transmission
-
ON- No alarms
–
OFF- Units not configured
–
Power supply ON/OFF
-
-
-
Internal communication between the KNX PCB and the H-LINK PCB.
-
Normal software operation
Description