Hitachi PC-ARF Technical Catalogue page 544

Table of Contents

Advertisement

6 Building air conditioning controls
CSNET Manager LT/XT

BMS configuration
Modbus Configuration
CSNET Manager allows to configure the BMS system in CSNET WEB devices by setting the ID for each indoor unit. This
configuration will link the BMS with the H-LINK.
To open the BMS configuration click on the change button. After clicking the button a dialogue will appear and you could
start to set the configuration.
BMS Configuration for Packaged
In this dialogue you can enable the BMS to activate this option, and after this, set in each row the unit information.
-
OU is the outdoor unit number.
-
IU is the indoor unit number.
-
Location is the location field of the unit. This field is only editable from the unit setting tab.
-
ID field is automatically set and is not modifiable.
CSNET Manager automatically assigns an ID for each found unit. You can change this ID on the table.
The ID field can not be repeated, if it will occurs, CSNET WEB will ask you to change the repeated ID.
In case of Packaged, "Auto Set Id" button will be available. This button open a new window when user could automatically
assign the ID to the units. This assignation could be done in two ways:
H-LINK I: BMS ID = OU x 16 + IU.
-
-
H-LINK II: BMS ID is assigned following the order of OU & IU.
Export buttons
Save to file button writes in a selected comma-separated values file the content of the table.
Copy to clipboard button will set in your clipboard the content of the table, separating the information by tabs.
In both cases the information of the table is ready to create an easy view of the information and an easier exportation to
other programs like Excel.
528
528
TCGB0106 rev.0 - 12/2014

Advertisement

Table of Contents
loading

Table of Contents