5 Centralised remote controls
PSC-A64S

DIP switch setting
Pin Nº
Contents
1
2
For address setting
3
DSW1
Simultaneous use of other
4
central controller
External Input Function
1
Changeover Operation
Stoppage Level/Pulse
External Input Function
2
Changeover
DSW2
Demand / Emergency Stop
3
Not prepared
4
H-LinkII Adaptive
N O T E
The DIP switches are all deactivated before they are sent from the factory.
Address setting with DSW1 Dip Switch
If connecting more than one central control (up to a maximum of 8) to the H-LINK system, first set the address using the
DIP switch DSW1, as shown below:
Address 1
Address 2
N O T E
If using the central station PSC-5S and PSC-A64S together in the same H-LINK (control line) system, set the DSW1 not to be overlapped
374
TCGB0106 rev.0 - 12/2014
DSW2
DSW1
Setting of DSW
OFF
Refer to the description
NO
Level
Emergency
Demand
Stoppage
-
Adaptive
Non-Adaptive
Address 3
Address 4
PSC-A64S
ON
For connecting plural central stations with H-LINK
(control line), the adress setting for each central sta-
tion is required
When using the following central controllers simulta-
neously, set the DSW1-4 pin ON
YES
- CS NET WEB
- CS NET Manager
Pulse
- Available only when the DSW2-1 pin is OFF.
- Pulse Stop when the DSW2-1 pin is ON.
-
Set OFF
- Set DSW2-4 pin OFF: H-LINK II adaptive.
- Set DSW2-4 pin ON: Non-H-LINK II adaptive.
Address 5
Address 6
Remarks
Address 7
Address 8