Hitachi PC-ARF Technical Catalogue page 460

Table of Contents

Advertisement

6 Building air conditioning controls
CSNET WEB (PSC-A160WEB1)
Address
Name
(Note 1)
18
TLIQUID
19
ERROR_CODE
20
STOP_CAUSE
21
VALVE_OPEN
22
OPER_CONDITION
23
DEFROST
24
AMBIENT_TEMP
25
POWER_GROUP
26
TIMER_DISABLED
27
OPTIONS
28
POWER
29
~
RESERVED
31
N O T E
1. Offset position is: 20000 + N*32 + Address as shown in table, where N is unit address. Unit address as set in CSNET WEB BMS con-
figuration dialog. Be careful because we are using address 0 as first register and in Mobdus could be used number 1 as first value. In
that case, it will be necessary to add 1 to the address calculation.
2. These numbers refer to signed 16-bit value using 2-complement format for negative values.
3. In case that the installation will use more than one CSNET WEB, it will use different device Ids, using Virtual Ids. Refer to the configura-
tion of your BMS to Ethernet adapter to know how it works.
4. Register number 10 is used for general alarm status.
444
444
TCGB0106 rev.0 - 12/2014
Description
Liquid pipe temperature (Note 2)
Alarm code
Compressor stop cause
Indoor unit expansion valve opening
Unit operation condition
0: OFF
1: Thermo OFF
2: Thermo ON
3: Alarm
Defrost
Ambient temperature (Note 2)
Power meter group
Timer disabled
0: Disabled
1: Enabled
Options setting
Calculated power consumption
Reserved for future use
Read/Write
Read
Read
Read
Read
Read
Read
Read
Read
Read/Write
Read
Read
Not used