Hitachi PC-ARF Technical Catalogue page 696

Table of Contents

Advertisement

7 Gateways for building management systems
HARC-BX E
SVNT
Unit
Variable num-
number
number
ber
28
4
nviOnOff_4
29
4
nviMode_4
nviSet-
30
4
Point_4
nvi-
31
4
FanSpeed_4
32
4
nviProtect_4
33
4
nvoOnOff_4
nvoIn-
34
4
letTemp_4
35
5
nviOnOff_5
36
5
nviMode_5
nviSet-
37
5
Point_5
nvi-
38
5
FanSpeed_5
39
5
nviProtect_5
40
5
nvoOnOff_5
nvoIn-
41
5
letTemp_5
680
680
TCGB0106 rev.0 - 12/2014
LONMARK
Type
SNVT No.
SNVT_switch
95
SNVT_hvac_
108
mode
SNVT_
105
temp_p
SNVT_switch
95
SNVT_switch
95
SNVT_state
83
SNVT_
105
temp_p
SNVT_switch
95
SNVT_hvac_
108
mode
SNVT_
105
temp_p
SNVT_switch
95
SNVT_switch
95
SNVT_state
83
SNVT_
105
temp_p
Description
Byte 1: Value 0 (Fixed)
On/Off order
Byte 2: State 0 = STOP
1 byte:
1 = HVAC_HEAT (Heat-
ing)
3 = HVAC_COOL (Cool-
Operation mode
ing)
setting
5 = HVAC_PRE_COOL
(Dehumidification)
9 = HVAC_FAN_ONLY
(Ventilation)
2 Bytes: 1700 ~ 3000 = 17
Temperature setting
~ 30 ºC
Byte 1: Value 1: Low,
Fan speed setting
Byte 2: State 0 (Fixed)
Byte 1: Value 0 (Fixed)
Byte 2: State 0: RCS
Remote control order
enabled
32 bits:
ON/OFF state and
bit 0: 0 (STOP)/1 (RUN)
alarm notification
bit 1: 0 (Normal) /1
(Alarm)
Indoor temperature
2 Bytes: -6200 ~ 12700 =
reading
-62 ~ 127 ºC
Byte 1: Value 0 (Fixed)
On/Off order
Byte 2: State 0 = STOP
1 byte:
1 = HVAC_HEAT (Heat-
ing)
3 = HVAC_COOL (Cool-
Operation mode
ing)
setting
5 = HVAC_PRE_COOL
(Dehumidification)
9 = HVAC_FAN_ONLY
(Ventilation)
2 Bytes: 1700 ~ 3000 = 17
Temperature setting
~ 30 ºC
Byte 1: Value 1: Low,
Fan speed setting
Byte 1: Value 0 (Fixed)
Byte 2: State 0: RCS
Remote control order
enabled
32 bits:
ON/OFF state and
bit 0: 0 (STOP)/1 (RUN)
alarm notification
bit 1: 0 (Normal) /1
(Alarm)
Indoor temperature
2 Bytes: -6200 ~ 12700 =
reading
-62 ~ 127 ºC
Condition
Note
State 1 = RUN
Allow an in-
terval of at
least 5 sec.
between 2
consecu-
tive orders
to any unit
on a H-Link
Value 2: Middle,
Value 3: High
enabled
State 1: RCS
disabled
Approxi-
mate up-
date time of
80 sec.
State 1 = RUN
Allow an in-
terval of at
least 5 sec.
between 2
consecu-
tive orders
to any unit
on a H-Link
Value 2:
Middle,Value 3:
HighByte 2: State
0 (Fixed)
enabled
State 1: RCS
disabled
Approxi-
mate up-
date time of
80 sec.