7 Gateways for building management systems
HARC-BX E
SVNT
Unit
Variable num-
number
number
ber
43
6
nviMode_6
nviSet-
44
6
Point_6
nvi-
45
6
FanSpeed_6
46
6
nviProtect_6
47
6
nvoOnOff_6
nvoIn-
48
6
letTemp_6
49
7
nviOnOff_7
50
7
nviMode_7
nviSet-
51
7
Point_7
nvi-
52
7
FanSpeed_7
53
7
nviProtect_7
54
7
nvoOnOff_7
nvoIn-
55
7
letTemp_7
56
Outdoor nviAllOnOff
nciMaxSend-
57
Time
nciMinSend-
58
Time
59
nciPwrUp
HARC-BX(A) XIF file variables list
681
681
TCGB0106 rev.0 - 12/2014
LONMARK
Type
SNVT No.
SNVT_hvac_
108
mode
SNVT_
105
temp_p
SNVT_switch
95
SNVT_switch
95
SNVT_state
83
SNVT_
105
temp_p
SNVT_switch
95
SNVT_hvac_
108
mode
SNVT_
105
temp_p
SNVT_switch
95
SNVT_switch
95
SNVT_state
83
SNVT_
105
temp_p
SNVT_switch
95
107
107
107
Description
1 byte:
1 = HVAC_HEAT (Heat-
ing)
3 = HVAC_COOL (Cool-
Operation mode
ing)
setting
5 = HVAC_PRE_COOL
(Dehumidification)
9 = HVAC_FAN_ONLY
(Ventilation)
2 Bytes: 1700 ~ 3000 = 17
Temperature setting
~ 30 ºC
Byte 1: Value 1: Low,
Value 2: Middle,
Fan speed setting
Value 3: High
Byte 2: State 0 (Fixed)
Byte 1: Value 0 (Fixed)
Byte 2: State 0: RCS
Remote control order
enabled
enabled
State 1: RCS
disabled
32 bits:
ON/OFF state and
bit 0: 0 (STOP)/1 (RUN)
alarm notification
bit 1: 0 (Normal) /1
(Alarm)
Indoor temperature
2 Bytes: -6200 ~ 12700 =
reading
-62 ~ 127 ºC
Byte 1: Value 0 (Fixed)
On/Off order
Byte 2: State 0 = STOP
State 1 = RUN
1 byte:
1 = HVAC_HEAT (Heat-
ing)
3 = HVAC_COOL (Cool-
Operation mode
ing)
setting
5 = HVAC_PRE_COOL
(Dehumidification)
9 = HVAC_FAN_ONLY
(Ventilation)
2 Bytes: 1700 ~ 3000 = 17
Temperature setting
~ 30 ºC
Byte 1: Value 1: Low,
Value 2: Middle,
Fan speed setting
Value 3: High
Byte 2: State 0 (Fixed)
Byte 1: Value 0 (Fixed)
Byte 2: State 0: RCS
Remote control order
enabled
enabled
State 1: RCS
disabled
32 bits:
ON/OFF state and
bit 0: 0 (STOP)/1 (RUN)
alarm notification
bit 1: 0 (Normal) /1
(Alarm)
Indoor temperature
2 Bytes: -6200 ~ 12700 =
reading
-62 ~ 127 ºC
Byte 1: Value 0 (Fixed)
On/Off order
Byte 2: State 0 = STOP
State 1 = RUN
Condition
Note
Approxi-
mate up-
date time of
80 sec.
Allow an in-
terval of at
least 5 sec.
between 2
consecu-
tive orders
to any unit
on a H-Link
Approxi-
mate up-
date time of
80 sec.
The use of
standard
values is
recom-
mended
(do not
change)
7