4 Individual remote controls
PC-ARF
Table B Input and Output Number Display and Connectors
Input number display
Input/Output indication
Input 1
Input 2
Output 1
Output 2
Output 3
Table C Input and Output Settings and Display Codes
Indication
00
Not set
01
Room Thermostat (for Cooling)
02
Room Thermostat (for Heating)
03
Remote ON/OFF 1 (Level)
04
Remote ON/OFF 2 (Operation)
05
Remote ON/OFF 2 (Stoppage)
06
Forbidding Remote Control after Manual Stoppage
07
Remote Cooling / Heating Change
08
Elevating Grille Input
N O T E
After at least 3 minutes from the power ON, change the optional setting.
The elevating grille input can be set to "Input 2" only.
The elevating grille cannot be set to "Input 1".
The elevating grille output can be set to "Output 1" or "Output 2" only.
The elevating grille output cannot be set to "Output 3".
Do not set the elevating grille for the total heat exchanger.
Record the setting conditions for each input and output in the "Setting" column of the table.
73
TCGB0106 rev.0 - 12/2014
Port
CN3 1-2
Remote ON/OFF 1 (Level)
CN3 2-3
Prohibiting Remote Control after Manual Stoppage
CN7 1-2
Operation
CN7 1-3
Alarm
CN8 1-2
Thermo-ON for Heating
Input
Factory setting
Setting item
Output
Not set
Operation
Alarm
Cooling
Thermo-ON for Cooling
Heating
Thermo-ON for Heating
Total Heat Exchanger
Elevating Grille Output
Indication
03
06
01
02
06
4