2 Control solutions
Great control possibilities

Options for detecting the room temperature
The room temperature value can be obtained from different ways:
1 By the air inlet temperature value at the indoor unit.
2 By the temperature value at the thermistor of the remote control (If available).
3 By the average between both previous values.
Moreover, HITACHI offers the remote temperature sensor THM-R2AE in order to provide more options for the room tem-
perature measurement. In this case, the room temperature value is obtained as follows:
1 By the average between the air inlet temperature value at the indoor unit and the temperature detected at the remote
sensor.
2 By the temperature value at the thermistor of the remote control (If available).
3 By the average between all the previous values.

Zoning systems compatibility
Zoning systems, in a ducted air-conditioning installation, allows having an individual control of the temperature in each
room. HITACHI ducted indoor units, RPI(M) units since FSN2E series, can be fully compatible with AIRZONE systems,
zone-based climate-control systems, thanks to the HITACHI-AIRZONE communication gateway (HITI11001).
The HTI11001 is commercialised directly by AIRZONE.