7 Gateways for building management systems
KNX001
Each of the previous signals must be associated with an address of Group KNX, so that the whole set behaves
as one more part of the KNX system with the same configuration and operation characteristics.
EIB
KNX
HGT
Configuration Soft-
ware
KNX001 performs continuous polling (reading) of all the signals configured in CSNET WEB and keeps their status updated
in order to serve as information to the KNX system.
When a change of status is detected in a signal, a written message is sent to the KNX bus of the associated KNX Group.
When a written message is received from the KNX bus to a KNX Group that is associated with the signal, the correspond-
ing message is sent immediately to CSNET WEB so that is can perform the appropriate action.
In the initial process after start-up of KNX001, a search is performed for the configured units (machines). If no unit is de-
tected, this is indicated by the communication error signal associated with each unit.

7.3.4.2 Limitations

Element
No. Packaged
No. KNX Groups
No. Listening addresses
No. Listening addresses per KNX Group

7.3.4.3 The KNX System

This section gives a general description of the KNX perspective.

Description
KNX001 is connected directly to the KNX bus, and behaves as one more part of the KNX system with the same configu-
ration and operation characteristics.
Internally, the electronic circuit that is connected to the KNX bus is optoisolated from the power supply and from the rest
of the equipment's electronics.
KNX001 receives, manages and sends all the messages from the KNX bus that refer to its configuration and operation.
On receiving messages sent to addresses of the KNX group, it sends the corresponding messages to CS-NET-WEB, in
order to keep both systems synchronized.
When a change in the signal from CSNET WEB is detected, the message is sent to the KNX bus of the associated KNX
group address, in order to keep both systems synchronized.
The status of the KNX bus is checked continuously. If loss of bus is detected, due for example to a power failure in the
KNX bus, when the KNX bus is restored KNX001 will detect it and will perform the Updates of the groups marked with
this property, i.e. it will make read requests for the group addresses. This behaviour can be disabled.
653
653
TCGB0106 rev.0 - 12/2014
KNX001
EIB
Ethernet
RS232
Only during configuration
Maximum
128
No. IU A/C
5920
Total no. of KNX Groups that can be used in KNX001
1000
No of KNX groups that can be used as listening addresses
255
No. listening addresses that can be associated with a KNX group
IU
CSNET WEB
H-Link
Notes
IU
IU
7