8 Control support devices
PSC-6RAD
ii. When using the cover. It can be installed at the right and left side of room air-conditioner. Double-face tape fixes
the cover and RAC adapter.
Example of installation:
b. In case that it cannot be installed to the wall due to the space or material problem, double-face tape is used for
installation on the room air-conditioner.
i. Confirm if the piping cover of the Unit can be removed when performing the service maintenance, and then fix
RAC adapter in the side of room air-conditioner with double-face tape. (Available at the right as well as left side)
ii. Clean with a dry cloth the surface to be installed.
N O T E
Consider the following points since the adhesivity changes according to the environmental conditions (temperature, humidity etc).
The adhesivity is decreased in the humidity or oil.
Warm the adhesive part and installation place of Double-face tape to avoid the decrease of the adhesivity in case that ambient tem-
perature is low.
Do not touch the adhesive part by fingers nor re-use it many times.
Any forced power shall not be added in 24 hours after the installation.
712
TCGB0106 rev.0 - 12/2014
RAC
adapter
Room Air-conditioner
Wiring outlet
Keep a distance
of 10mm
Room Air-conditioner
RAC adapter
Cover
Fix it to RAC adapter with the
enclosed double-face tape
40 mm
Cover
40 mm