4 Individual remote controls
PC-ART
Content of check mode 2
When more than three indoor units are connected to one remote control, only the most recent data from the three first
indoor units connected in sequence will be shown.
Pressing "" on the TEMP button takes you to the next screen, while pressing "" on the same button takes you to the
previous screen.
Step
No.
1
Indoor unit air inlet temperature in the thermistor (°C).
2
Indoor unit discharge air temperature in thermistor (°C).
3
Indoor unit heat exchanger liquid piping temperature (freeze protection) (°C).
4
Outdoor temperature (°C).
5
Indoor unit heat exchanger gas piping temperature (°C).
6
Evaporating temperature in heating mode (°C).
Control information
7
- Indicates internal remote control information. It has no specific meaning.
Temperature of the discharge gas in the top of compressor chamber (°C).
8
- When two components are running simultaneously, the average temperature is given.
N O T E
Possible abnormal conditions
TEMPERATURE INDICATION
--
129
FF
255
or
127
During transitory periods, such as on start-up, the "--" or "00" indicator may appear for a limited time.
153
TCGB0106 rev.0 - 12/2014
Temperature indication
Open circuit on any thermistor except
129
Open circuit in compressor discharge
thermistor
Short-circuit in any thermistor except
127
Short-circuit in compressor discharge
thermistor
Indication of temperature, etc.
Category code indication
FAULT
Check that the PCB is not read-
ing the thermistor incorrectly.
Consult the "PCB self-checking
procedure using the remote con-
trol" section
91
23
4
92
50
93
25
12
94
95
25
96
03
--
97
98
45