Hitachi PC-ARF Technical Catalogue page 241

Table of Contents

Advertisement

5 Centralised remote controls
PSC-A64GT
Main breaker switch
Model
Supply voltage
PC-A64GT
1~ 230V 50 Hz
(1) ELB: earth leakage breaker (field-supplied)
(2) CB: circuit breaker (field-supplied)
C A U T I O N
When using an AC200V to 240V power supply.
In case of using a 200V~240V power supply, diverge the main power supply cables by using a pull box as shown in the figure.
The electricity supply to the unit should be via an exclusive power control switch and protective circuit breaker, certified and installed
in accordance with local or national safety regulations.
Use an earth leakage breaker with medium sensitivity, and an activation speed of 0.1 or less. If this is not fitted, there is a risk of electric
shock and/or fire.
Install an earth leakage breaker, fuse and circuit breaker for each outdoor unit power line. Not fitting it may cause an electric shock
or fire.
D A N G E R
Turn OFF the main power switch for the indoor units, outdoor units, and central stations before the electrical wiring work is performed.
If not, it may cause a fire, electrical shock or device breaking down.
Do not use cables that are lighter than the normal flexible coated polychloroprene cable (code H05RN-F).

DIP switch adjustment
The list for switch settings of central stations is shown in the following table.
1 Apply switch settings as appropriate.
Switch
Switch No.
RSW1
-
(Rotary Switch
16-poles)
1
DSW1
2
(Dip Switch 4-poles)
3
4
1
DSW2
(Dip Switch 2-poles)
2
SW1
-
225
TCGB0106 rev.0 - 12/2014
Maximum current
(A)
Rated current (A)
5
To outdoor unit or power
circuit breaker
Pull box
PSC-A64GT
Indoor units
Usage
For address setting of central station
ON: Setting for Non-H-LINK II
OFF: Setting for H-LINK II
OFF (Fixed)
OFF (Fixed)
OFF (Fixed)
ON: Terminating Resistance Enable
OFF: Terminating Resistance Disable
ON: Protection Fuse for H-LINK ... Disable
(Short-circuited)
OFF: Protection Fuse for H-LINK ... Enable
(Normal)
ON: Turn ON Central Station
OFF: Turn OFF Central Station
ELB(1)
Sensitivity (mA)
40
30
Factory
Setting
When using multiple units of the cen-
0
tral stations. (*)
OFF
Refer to the chart in the next page.
OFF
Not Used
OFF
Not Used
OFF
Not Used
Make sure no other terminating resist-
ance exists on the same H-LINK when
OFF
enabling the terminating resistance
from the central station.
OFF
ON
CB(2)
Rated current (A)
5
5
Remarks