CompoBus/S Specifications
Note Before inserting the signal wires, make sure that the screws have been loosened sufficiently. If a
screw is too tight when a wire is inserted, the wire may go into the gap in the rear of the fitting
instead of going into the proper place. If this happens, the wire cannot be securely fastened.
3. Tighten the cable terminal block screws to the proper torque of 0.5 N m for each signal wire. Use a
small flat-head screwdriver with of uniform thickness. A normal screwdriver which is thin only at the
end will not fit all the way in.
Note The XW4Z-00C Screwdriver is available from OMRON especially for this task.
The A1 Series by Phoenix Contact is recommended as a crimp-stye terminal for the cable. Phoenix
Contact also supplies the ZA3 as a special-purpose tool.
4. Be careful to match the directions of the cable terminal block and the Position Driver's terminal
block, and insert the cable terminal block. Be sure to push it all the way in.