Design and Installation
j Connecting FND-X50H-
Connect an external Regenerative
Resistor if the regeneration capacity
in the Position Driver is not sufficient.
The external Regenerative Resistor
can heat to 120 C. Install the Resistor
so that heating will not cause adverse
affects.
Regenerative Resistor
100W: R88A-RR20030
200 W: R88A-RR40030
DIO Position Drivers:FND-CCX
General-purpose Control Cable
CompoBus/S Position Drivers: Communications Cable
(SCA1-4F10 Flat Cable or commercially available VCTF cable (VCTF JIS C3306 2-core 0.75mm
Note When using the CompoBus/S Position Drivers, create the same sequence using the ALM bit.
2-86
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Position Drivers to Peripheral Devices
Three-phase, 200/240 VAC, 50/60 Hz (FND-X50H- )
Main-circuit
power supply
OMNUC FND-X-series
Position Driver
TB
R
P
J
Protectively
separated
CN1
(CONT)
28 ALM
19 OGND
S
Main-circuit connector
Surge killer
OMNUC U-series (1 to 2 kW)
Power Cables
R88A-CAUB
S
R88A-CAUB
B
Ground (to 100 Ω
or less)
OMNUC U-series (1 to 2 kW) Encoder Cable
(Incremental or Absolute)
R88A-CRUB
N
OMNUC M-series Resolver Cable
R88A-CRM
N + R88A-CRM0RST
24 VDC
(See note)
2
Chapter 2
Servo error display
OMNUC U/M-series
AC Servomotor
))