Design and Installation
j Harmonic Current Suppression
An AC Reactor that controls steep current changes is used for suppressing harmonic current.
Guidelines issued by MITI in September 1994 regarding countermeasures for harmonic suppression
of domestic or general-purpose electric appliances require measures that control the flow of harmonic
current to the power supply line.
Select an appropriate AC Reactor depending on the Position Driver to be used.
When using a single-phase power supply, one connection terminal will become open. Be sure to insu-
late this terminal with insulation tape, etc.
Connection Example
FND-X06
AC Reactor
Application Specifications
Drivers
3G3IV-PUZBAB5A2.1MH
FND-X06L-
FND-X12L-
FND-X06H-
3G3IV-PUZBAB2.5A4.2MH
FND-X12H-
3G3IV-PUZBAB5A2.1MH
FND-X25H-
3G3IV-PUZBAB10A1.1MH
FND-X50H-
3G3IV-PUZBAB20A0.53MH
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
to -X25
FND-X
Model
5 A
2.5 A
5 A
10 A
20 A
FND-X50
AC Reactor
AC Reactor
Rated
Inductance
current
2.1 mH
4.2 mH
2.1 mH
1.1 mH
0.53 mH
Chapter 2
FND-X
Loss
Weight
15 W
2.5 kg
g
15 W
2.5 kg
15 W
2.5 kg
25 W
3 kg
35 W
3 kg
2-83