Checking The Installation Space - YASKAWA FSDrive-MV1000 Instructions Manual

Super energy-saving medium-voltage ac drive
Hide thumbs Also See for FSDrive-MV1000:
Table of Contents

Advertisement

2.2 Mechanical Installation

◆ Checking the Installation Space

Secure the space indicated below around the drive to maintain sufficient cooling.
Note: If the installation space for the drive is restricted and the space indicated below cannot be secured, contact your Yaskawa
representatives or the nearest Yaskawa sales office.
Figure 2.1
A
B
A – Min. 1000 mm
B – Min. 30 mm
C – Min. 2000 mm
Installation
Space
Sufficient space to remove the cooling fans from the top of the drive is required for fan replacement. Air is expelled
A (Top)
through the cooling fans on top of the drive. If the cooling fans are too close to the ceiling, the air that has been expelled
may be drawn back into the drive, reducing the cooling performance.
B (Sides)
Sufficient space is required to allow Power Cells to be drawn out and placed on the lifter used to convey them when
C (Front)
Power Cells need to be replaced.
D (Rear)
Sufficient working space is required to route the cables and to install anchors on the back of the drive.
36
Front views
Figure 2.1 Drive Installation Space
Table 2.2 Precautions on Installation Space
Front
B
C
Door opening dimension
Door opening dimension
D – Min. 600 mm
E – Max. 800 mm
Details
YASKAWA ELECTRIC EZZ010928 FSDrive-MV1000 Instructions
Rear
D
E
Side view

Hide quick links:

Advertisement

Table of Contents
loading