u Installation Space
Figure 2.1
shows the installation distance required to maintain sufficient space for airflow and wiring.
Note: If the installation space for the drive is restricted and the space indicated in the figures below cannot be secured, contact your
Yaskawa representatives or the nearest Yaskawa sales office.
Figure 2.1
A
B
A – Min. 1000 mm
B – Min. 30 mm
C – Min. 2000 mm
Installation
Space
The drive requires sufficient space at the top for the replacement of the cooling fans and to cool the drive. Air is
A (Top)
expelled through the cooling fans on top of the drive. If the cooling fans are too close to the ceiling, the air that has been
expelled may be drawn back into the drive and reduce the cooling performance.
Although side-by-side installation with other panels is possible, the factory recommends ensuring at least 30 mm
B (Sides)
spacing is available between panels.
Sufficient space is required to allow Power Cells to be drawn out and placed on the lifter to move them during
C (Front)
replacement.
D (Rear)
Sufficient working space is required to route the cables and to install anchors on the back of the drive.
E (Front)
Sufficient working space is required to open the door.
YASKAWA ELECTRIC TOEP C710687 02B FSDrive-MV1000 Instructions
Front views
Figure 2.1 Drive Installation Space
Table 2.2 Precautions on Installation Space
Asia
Front
B
C
Door opening dimension
Door opening dimension
E
D – Min. 600 mm
E – Max. 800 mm
Details