2.2 Mechanical Installation

2.2
Mechanical Installation
This section outlines specifications, procedures, and the environment for proper mechanical installation of the drive.
u

Installation Environment

Install the drive in an environment matching the specifications below to help prolong the optimum performance life of the
drive.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Avoid placing drive peripheral devices, transformers, or other electronics near the drive as the noise created can lead to erroneous
operation. If such devices must be used in close proximity to the drive, take proper steps to shield the drive from noise.
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the drive during installation. Failure to comply
could result in damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before
drive start-up, as the cover will reduce ventilation and cause the drive to overheat.
u

Installation Orientation and Spacing

Install the drive upright as illustrated in
40
Table 2.1 Installation Environment
Indoors
-10 °C to +40 °C (IP20/NEMA Type 1)
-10 °C to +50 °C (IP00/Open-Chassis)
Drive reliability improves in environments without wide temperature fluctuations.
When using the drive in an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air
temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20 to +60 °C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m or lower, up to 3000 m with derating.
2
10 to 20 Hz at 9.8 m/s
, 20 to 55 Hz at 5.9 m/s
Install the drive vertically to maintain maximum cooling effects.
Figure 2.1
OK
Figure 2.1 Correct Installation Orientation
Conditions
Refer to Drive Derating Data on page 377
2
to maintain proper cooling.
Not OK
Not OK
YASKAWA ELECTRIC SIEP C710616 31B YASKAWA AC Drive – A1000 Technical Manual