2.2 Mechanical Installation

2.2
Mechanical Installation
This section outlines specifications, procedures, and environment for proper mechanical installation of the drive.

Installation Environment

u
To help prolong the optimum performance life of the drive, install the drive in the proper environment. The table below provides description of the
appropriate environment for the drive.
Environment
Installation Area
Ambient Temperature
Humidity
Storage Temperature
Surrounding Area
Altitude
Vibration
Orientation
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during installation and project construction. Failure to comply could result in
damage to the drive. Place a temporary cover over the top of the drive during installation. Remove the temporary cover before start-up, as the cover will reduce ventilation and
cause the drive to overheat.
u

Installation Orientation and Spacing

Install the drive upright as illustrated in
Single Drive Installation
n
To maintain sufficient space for airflow and wiring, refer to
the heatsink.
26
Table 2.1 Installation Environment
Indoors
-10°C to +40°C (IP20/NEMA Type 1)
-10°C to +50°C (IP20/Open-Chassis)
Drive reliability improves in environments without wide temperature fluctuations.
When using an enclosure panel, install a cooling fan or air conditioner in the area to ensure that the air temperature inside the enclosure does not exceed the
specified levels.
Do not allow ice to develop on the drive.
95% RH or less and free of condensation
-20°C to +60°C
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight
1000 m or lower
10 to 20 Hz at 9.8 m/s
2
20 to 55 Hz at 5.9 m/s
2
Install the drive vertically to maintain maximum cooling effects.
Figure 2.1
to maintain proper cooling.
A
A – Correct
Figure 2.1 Correct Installation Orientation
Figure 2.2
Conditions
B
B
B – Incorrect
. Install the heatsink against a closed surface to avoid diverting cooling air around
YASKAWA ELECTRIC SIEP C710606 18A YASKAWA AC Drive – V1000 Technical Manual (Preliminary)