3.6

Power Supply

Pos : 19.16.2 /Serie 750 ( WAGO-I/O- SYST EM)/Ansc hließ en/Ei ns peis ekonzepte/XTR-Koppler-/C ontroll er und 750-613/040-000: Eins peisung aus SELV-/PELV-N etzger äten vorgesc hrieben @ 29\mod_1495116623787_21.doc x @ 422203 @ @ 1
The system power supply and field power supply must be powered via
SELV/PELV power supply units.
Pos : null /Alle Serien ( Allgemei ne Modul e)/Ü bersc hriften/Ebene 3/Ü bers tromsc hutz - Übersc hrift 3 @ 31\mod_1523371183064_21.doc x @ 481017 @ 3 @ 1
3.6.1

Overcurrent Protection

Pos : null /Serie 750 (WAGO-I/O-SYST EM)/Ansc hließ en/Eins peis ekonzepte/Warnung: Mögliche Brandgefahr durch unz ureic henden Ü berstroms chutz! (bei Klei nspannung) @ 31\mod_1524745034627_21.doc x @ 483789 @ @ 1
Possible fire hazard due to insufficient overcurrent protection!
In the event of a fault, insufficient overcurrent protection can present a possible
fire hazard. In the event of a fault, excessive current flow in the components can
cause significant overheating. Therefore, you should always dimension the
overcurrent protection according to the anticipated power usage.
Pos : null /Serie 750 (WAGO-I/O-SYST EM)/Ansc hließ en/Eins peis ekonzepte/Ü berstromsc hutz bei Kleinspannung ( XTR) @ 31\mod_1524130657135_21.doc x @ 482309 @ @ 1
The system and field voltage of the WAGO I/O SYSTEMs 750 XTR is supplied on
the head stations and bus supply modules.
For components that work with extra low voltage, only SELV/PELV voltage
sources should be used.
A single voltage source supplying multiple components must be designed
according to the component with the strictest electrical safety requirements.
For components which are only allowed to be supplied by SELV voltage sources,
these requirements are listed in the technical data.
Most components in the WAGO-I/O-SYSTEM 750 XTR have no internal
overcurrent protection. Therefore, appropriate overcurrent production must
always be implemented externally for the power supply to these components,
e.g. via fuses.
The maximum permissible current is listed in the technical data of the
components used.
Pos : null /Serie 750 (WAGO-I/O-SYST EM)/Ansc hließ en/Eins peis ekonzepte/Ac htung: Sys temvers orgung nur mit geeigneter Absic her ung! @ 31\mod_1523371427560_21.doc x @ 481022 @ @ 1
System supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
If you implement the overcurrent protection for the system supply with a fuse, a
fuse, max. 2 A, slow-acting, should be used.
Pos : null /Serie 750 (WAGO-I/O-SYST EM)/Ansc hließ en/Eins peis ekonzepte/Ac htung: Fel dvers orgung nur mit g eeigneter Absicherung! @ 31\mod_1523372916706_21.doc x @ 481026 @ @ 1
Field supply only with appropriate fuse protection!
Without overcurrent protection, the electronics can be damaged.
If you alternatively implement the overcurrent protection for the field supply with
an external fuse, a 10 A fuse should be used.
Pos : 19.16.8 /Serie 750 ( WAGO-I/O- SYST EM)/Sys tembesc hrei bung/Vers orgung/Potenti altrennung @ 3\mod_1232950094125_21.doc x @ 26732 @ 3 @ 1
Manual
Version 1.3.0
WAGO-I/O-SYSTEM 750 XTR
750-352/040-000 FC ETHERNET G3 XTR