Parameter Descriptions
6-74 Terminal X45/1 Output Timeout Preset
Range:
Function:
0.00%
[0.00 -
Holds the preset level of Analog Output 3
*
100.00%]
(terminal X45/1).
In case of a bus timeout and a timeout
function is selected in par. 6-70 Terminal
X45/1 Output the output will preset to this
level.
3.8.9 6-8* Analog Output 4 MCB 113
Parameters for configuring the scaling and limits for analog
output 4. Terminal X45/3 and X45/4. Analog outputs are
current outputs: 0/4 – 20 mA. Resolution on analog output is
11 bit.
6-80 Terminal X45/3 Output
Option:
Function:
Select the function of Terminal X45/3 as an
analog current output.
[0]
No operation Same selections available as for
*
par. 6-70 Terminal X45/1 Output
6-81 Terminal X45/3 Output Min Scale
Option:
Function:
[0.00%]
0.00 -
Scales the minimum output of the selected
*
200.00%
analog signal on terminal X45/3. Scale the
minimum value as a percentage of the
maximum signal value, i.e. 0 mA (or 0 Hz) is
desired at 25% of the maximum output
value and 25% is programmed. The value
can never be higher than the corresponding
setting in par. 6-82 Terminal X45/3 Max.
Scale if value is below 100%.
This parameter is active when option
module MCB 113 is mounted in the
frequency converter.
6-82 Terminal X45/3 Output Max Scale
Option:
Function:
[0.00%]
0.00 -
Scales the maximum output of the selected
200.00%
analog signal on terminal X45/3. Scale the
*
value to the desired maximum value of the
current signal output. Scale the output to give
a lower current than 20 mA at full scale or 20
mA at an output below 100% of the maximum
signal value. If 20 mA is the desired output
current at a value between 0 - 100% of the ful-
scale output, program the percentage value in
the parameter, i.e. 50% = 20 mA. If a current
between 4 and 20 mA is desired at maximum
output (100%), calculate the percentage value
as follows (example where desired max. output
is 10 mA):
FC 300 Programming Guide
6-82 Terminal X45/3 Output Max Scale
Option:
6-83 Terminal X45/3 Output Bus Control
Option:
[0.00%]
6-84 Terminal X45/3 Output Timeout Preset
Option:
[0.00%]
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
I RANGE mA
I DESIRED MAX mA
mA
20 − 4
x
=
mA
10
Function:
0.00 - 100.00% Holds the level of output 4 (X45/3) if
*
controlled by bus.
Function:
0.00 -
Holds the present level of output 4
*
100.00%
(X45/3). In case of a bus timeout and a
timeout function is selected in
par. 6-80 Terminal X45/3 Output the
output will preset to this level.
x
100 %
100 % = 160 %
93