Parameter Descriptions
3.7.2 5-1* Digital Inputs
The digital inputs are used for selecting various functions in
the frequency converter. All digital inputs can be set to the
following functions:
3
3
Digital input function
No operation
Reset
Coast inverse
Coast and reset inverse
Quick stop inverse
DC-brake inverse
Stop inverse
Start
Latched start
Reversing
Start reversing
Enable start forward
Enable start reverse
Jog
Preset reference on
Preset ref bit 0
Preset ref bit 1
Preset ref bit 2
Freeze reference
Freeze output
Speed up
Speed down
Set-up select bit 0
Set-up select bit 1
Precise stop inverse
Precises start, stop
Catch up
Slow down
Counter input
Pulse input Edge Trigged
Pulse input Time Based
Ramp bit 0
Ramp bit 1
Mains failure inverse
Latched precise start
Latched precise stop
inverse
DigiPot Increase
DigiPot Decrease
DigiPot Clear
Digipot Hoist
Counter A (up)
Counter A (down)
Reset Counter A
Counter B (up)
Counter B (down)
Reset Counter B
68
FC 300 Programming Guide
Select
Terminal
[0]
All *term 32, 33
[1]
All
[2]
All *term 27
[3]
All
[4]
All
[5]
All
[6]
All
[8]
All *term 18
[9]
All
[10]
All *term 19
[11]
All
[12]
All
[13]
All
[14]
All *term 29
[15]
All
[16]
All
[17]
All
[18]
All
[19]
All
[20]
All
[21]
All
[22]
All
[23]
All
[24]
All
[26]
18, 19
[27]
18, 19
[28]
All
[29]
All
[30]
29, 33
[31]
29, 33
[32]
29, 33
[34]
All
[35]
All
[36]
All
[40]
18, 19
[41]
18, 19
[55]
All
[56]
All
[57]
All
[58]
All
[60]
29, 33
[61]
29, 33
[62]
All
[63]
29, 33
[64]
29, 33
[65]
All
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Mech. Brake Feedb.
Mech. Brake Feedb. Inv.
PID Error Inv.
PID Reset I-part
PID enable
PTC Card 1
FC 300 standard terminals are 18, 19, 27, 29, 32 and 33. MCB
101 terminals are X30/2, X30/3 and X30/4.
Terminal 29 functions as an output only in FC 302.
Functions dedicated to only one digital input are stated in the
associated parameter.
All digital inputs can be programmed to these functions:
[0]
No
No reaction to signals transmitted to the
operation
terminal.
[1]
Reset
Resets frequency converter after a TRIP/ALARM.
Not all alarms can be reset.
[2]
Coast
(Default Digital input 27): Coasting stop,
inverse
inverted input (NC). The frequency converter
leaves the motor in free mode. Logic '0' =>
coasting stop.
[3]
Coast and
Reset and coasting stop Inverted input (NC).
reset
Leaves motor in free mode and resets frequen-
inverse
cy converter. Logic '0' => coasting stop and
reset.
[4]
Quick stop
Inverted input (NC). Generates a stop in accord-
inverse
ance with quick-stop ramp time set in
par. 3-81 Quick Stop Ramp Time. When motor
stops, the shaft is in free mode. Logic '0' =>
Quick-stop.
[5]
DC-brake
Inverted input for DC braking (NC). Stops motor
inverse
by energizing it with a DC current for a certain
time period. See par. 2-01 DC Brake Current to
par. 2-03 DC Brake Cut In Speed [RPM]. The
function is only active when the value in
par. 2-02 DC Braking Time is different from 0.
Logic '0' => DC braking.
[6]
Stop inverse Stop Inverted function. Generates a stop
function when the selected terminal goes from
logical level '1' to '0'. The stop is performed
according to the selected ramp time
(par. 3-42 Ramp 1 Ramp Down Time,
par. 3-52 Ramp 2 Ramp down Time,
par. 3-62 Ramp 3 Ramp down Time,
par. 3-72 Ramp 4 Ramp Down Time).
NOTE
When the frequency converter is at
the torque limit and has received a
stop command, it may not stop by
itself. To ensure that the frequency
converter stops, configure a digital
output to Torque limit & stop [27] and
connect this digital output to a digital
input that is configured as coast.