Parameter Descriptions
3.10.2 8-1* Ctrl. Word Settings
8-10 Control Word Profile
Select the interpretation of the control and status words
corresponding to the installed fieldbus. Only the selections valid for
the fieldbus installed in slot A will be visible in the LCP display.
For guidelines in selection of FC profile [0] and PROFIdrive profile [1]
please refer to the Serial communication via RS 485 Interface section.
For additional guidelines in the selection of PROFIdrive profile [1],
ODVA [5] and CANopen DSP 402 [7], please refer to the Operating
Instructions for the installed fieldbus.
Option:
[0]
FC profile
*
[1]
PROFIdrive profile
[5]
ODVA
[7]
CANopen DSP 402
[8]
MCO
8-13 Configurable Status Word STW
Option:
Function:
This parameter enables configuration of bits
12 – 15 in the status word.
[0]
No function
The input is always low.
[1]
Profile Default Depended on the profile set in Parameter
*
8-10.
[2]
Alarm 68 Only The input will go high whenever Alarm 68 is
active and will go low whenever no alarm 68
is active
[3]
Trip excl Alarm
The input will go high whenever Trip on
68
other Alarms then Alarm 68 is active.
[10] T18 DI status.
The input will go high whenever T18 has 24V
and will go low whenever T18 has 0V
[11] T19 DI status.
The input will go high whenever T19 has 24V
and will go low whenever T19 has 0V
[12] T27 DI status.
The input will go high whenever T27 has 24V
and will go low whenever T27 has 0V
[13] T29 DI status.
The input will go high whenever T29 has 24V
and will go low whenever T29 has 0V
[14] T32 DI status.
The input will go high whenever T32 has 24V
and will go low whenever T32 has 0V
[15] T33 DI status.
The input will go high whenever T33 has 24V
and will go low whenever T33 has 0V
[16] T37 DI status
The input will go high whenever T37 has 0V
and will go low whenever T37 has 24V
[21] Thermal
The thermal warning turns on when the
warning
temperature exceeds the limit in the motor,
the frequency converter, the brake resistor,
or the thermistor..
[30] Brake fault
Will go high when the brake IGBT is short-
(IGBT)
circuited.
[40] Out of ref
If Comparator 0 is evaluated as TRUE, the
range
input will go high. Otherwise, it will be low.
[60] Comparator 0
If Comparator 0 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
FC 300 Programming Guide
8-13 Configurable Status Word STW
Option:
[61] Comparator 1
[62] Comparator 2
[63] Comparator 3
[64] Comparator 4
[65] Comparator 5
Function:
[70] Logic Rule 0
[71] Logic Rule 1
[72] Logic Rule 2
[73] Logic Rule 3
[74] Logic Rule 4
[75] Logic Rule 5
[80] SL Digital
[81] SL Digital
[82] SL Digital
[83] SL Digital
[84] SL Digital
[85] SL Digital
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
If Comparator 1 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
If Comparator 2 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
If Comparator 3 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
If Comparator 4 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
If Comparator 5 is evaluated as TRUE, the
input will go high. Otherwise, it will be low.
If Logic Rule 0 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
If Logic Rule 1 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
If Logic Rule 2 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
If Logic Rule 3 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
If Logic Rule 4 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
If Logic Rule 5 is evaluated as TRUE, the input
will go high. Otherwise, it will be low.
SL Controller Action. The input will go high
Output A
whenever the Smart Logic Action [38] Set
dig. out. A high is executed. The input will go
low whenever the Smart Logic Action [32]
Set dig. out. A low is executed.
SL Controller Action. The input will go high
Output B
whenever the Smart Logic Action [39] Set
dig. out. A high is executed. The input will go
low whenever the Smart Logic Action [33]
Set dig. out. A low is executed.
SL Controller Action. The input will go high
Output C
whenever the Smart Logic Action [40] Set
dig. out. A high is executed. The input will go
low whenever the Smart Logic Action [34]
Set dig. out. A low is executed.
SL Controller Action. The input will go high
Output D
whenever the Smart Logic Action [41] Set
dig. out. A high is executed. The input will go
low whenever the Smart Logic Action [35]
Set dig. out. A low is executed.
SL Controller Action. The input will go high
Output E
whenever the Smart Logic Action [42] Set
dig. out. A high is executed. The input will go
low whenever the Smart Logic Action [36]
Set dig. out. A low is executed.
SL Controller Action. The input will go high
Output F
whenever the Smart Logic Action [43] Set
dig. out. A high is executed. The input will go
low whenever the Smart Logic Action [37]
Set dig. out. A low is executed
3
3
101