How to Programme
It is possible to switch directly between Main Menu mode and
Quick Menu mode.
Parameter shortcut can be carried out by pressing down the
2
2
[Main Menu] key for 3 seconds. The parameter shortcut allows
direct access to any parameter.
[Alarm Log] displays an Alarm list of the five latest alarms
(numbered A1-A5). To obtain additional details about an
alarm, use the arrow keys to manoeuvre to the alarm number
and press [OK]. You will now receive information about the
condition of your frequency converter right before entering
the alarm mode.
[Back] takes you to the previous step or layer in the navigation
structure.
[Cancel] annuls your last change or command as long as the
display has not been changed.
[Info] supplies information about a command, parameter, or
function in any display window. [Info] provides detailed
information whenever help is needed.
Exit info mode by pressing either [Info], [Back], or [Cancel].
Navigation Keys
The four navigation arrows are used to navigate between the
different choices available in [Quick Menu], [Main Menu] and
[Alarm Log]. Use the keys to move the cursor.
[OK] is used for choosing a parameter marked by the cursor
and for enabling the change of a parameter.
Local Control Key for local control are found at the bottom of
the LCP.
[Hand On] enables control of the frequency converter via the
LCP. [Hand on] also starts the motor, and it is now possible to
enter the motor speed data by means of the arrow keys. The
key can be selected as Enable [1] or Disable [0] via
par. 0-40 [Hand on] Key on LCP
External stop signals activated by means of control signals or a
serial bus will override a "start" command via the LCP.
The following control signals will still be active when [Hand
on] is activated:
14
FC 300 Programming Guide
•
•
•
•
•
•
•
•
[Off] stops the connected motor. The key can be selected as
Enable [1] or Disable [0] via par. 0-41 [Off] Key on LCP. If no
external stop function is selected and the [Off] key is inactive
the motor can be stopped by disconnecting the voltage.
[Auto On] enables the frequency converter to be controlled
via the control terminals and/or serial communication. When a
start signal is applied on the control terminals and/or the bus,
the frequency converter will start. The key can be selected as
Enable [1] or Disable [0] via par. 0-42 [Auto on] Key on LCP.
NOTE
An active HAND-OFF-AUTO signal via the digital inputs
has higher priority than the control keys [Hand on] –
[Auto on].
[Reset] is used for resetting the frequency converter after an
alarm (trip). It can be selected as Enable [1] or Disable [0] via
par. 0-43 [Reset] Key on LCP.
The parameter shortcut can be carried out by holding down
the [Main Menu] key for 3 seconds. The parameter shortcut
allows direct access to any parameter.
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
[Hand on] - [Off] - [Auto on]
Reset
Coasting stop inverse
Reversing
Set-up select bit 0- Set-up select bit 1
Stop command from serial communication
Quick stop
DC brake