Parameter Descriptions
8-06 Reset Control Word Timeout
This parameter is active only when Hold set-up [0] has been
selected in par. 8-05 End-of-Timeout Function.
Option:
[0]
Do not reset Retains the set-up specified in par. 8-04 Control
*
3
3
[1]
Do reset
8-07 Diagnosis Trigger
Option:
100
FC 300 Programming Guide
Function:
Word Timeout Function, following a control
word time-out.
Returns the frequency converter to the original
set-up following a control word time-out. The
frequency converter performs the reset and
then immediately reverts to the Do not reset [0]
setting
Function:
This parameter enables and controls the frequency
converter diagnosis function and permits
expansion of the diagnosis data to 24 byte.
NOTE
This is only valid for Profibus.
-
Disable [0]: Do not send extended
diagnosis data even if they appear in the
frequency converter.
-
Trigger on alarms [1]: Send extended
diagnosis data when one or more alarms
appear in alarm par. 16-90 Alarm Word or
par. 9-53 Profibus Warning Word.
-
Trigger alarms/warn. [2]: Send extended
diagnosis data if one or more alarms or
warnings appear in alarm
par. 16-90 Alarm Word, par. 9-53 Profibus
Warning Word, or warning
par. 16-92 Warning Word.
The content of the extended diagnosis frame is as
follows:
Byte
Content
Description
0 - 5
Standard DP
Standard DP Diagnose
Diagnose
Data
Data
6
PDU length xx Header of extended
diagnostic data
7
Status type =
Header of extended
0x81
diagnostic data
8
Slot = 0
Header of extended
diagnostic data
9
Status info = 0 Header of extended
diagnostic data
10 - 13 VLT
VLT warning word
par. 16-92 Wa
rning Word
MG.33.M9.02 - VLT
8-07 Diagnosis Trigger
Option:
Function:
14 - 17 VLT
18 - 21 VLT
22 - 23 VLT
Enabling diagnosis may cause increased bus traffic.
Diagnosis functions are not supported by all
fieldbus types.
[0]
Disable
*
[1]
Trigger
on
alarms
[2]
Trigger
alarm/
warn.
8-08 Readout Filtering
The function is used if the speed feedback value readouts on
fieldbus are fluctuating. Select filtered if the function is required. A
power-cycle is required for changes to take effect.
Option:
[0]
Motor Data Std-
*
Filt.
[1]
Motor Data LP-
Filter
®
is a registered Danfoss trademark
VLT status word
par. 16-03 Stat
us Word
VLT alarm word
par. 16-90 Ala
rm Word
Communication
par. 9-53 Profi
warning word (Profibus)
bus Warning
Word
Function:
Select [0] for normal bus readouts.
Select [1] for filtered bus readouts
of the following parameters:
Par. 16-10 Power [kW]
Par. 16-11 Power [hp]
Par. 16-12 Motor Voltage
Par. 16-14 Motor Current
Par. 16-16 Torque [Nm]
Par. 16-17 Speed [RPM]
Par. 16-22 Torque [%]
Par. 16-25 Torque [Nm] High