Danfoss FC 300 Programming Manual page 120

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
12-37 COS Inhibit Timer
Range:
[0 – 65.535
ms]
3
3
12-38 COS Filters
Range:
[[0 - 9] Filter 0 – 9
(0000 - FFFFhex)]
3.13.5 12-8* Other Ethernet Services
12-80 FTP Server
Option:
[0]
Disable
*
[1]
Enable
12-81 HTTP Server
Option:
[0]
Disable
*
[1]
Enable
12-82 SMTP Service
Option:
[0]
Disable Disables the SMTP (e-mail) service on the option.
*
[1]
Enable
12-89 Transparent Socket Channel Port
Range:
0
[0 – 9999] Configures the TCP port-number for the transpar-
*
120
Function:
Read only Change-Of-State inhibit timer. If the
option is configured for COS operation, this inhibit
timer can be configured in the Forward Open
telegram to prevent that continuously changing
PCD data generates extensive network traffic. The
inhibit time is in milliseconds, 0 = disabled.
Function:
Change-Of-State PCD filters. Sets up a
filter mask for each word of process data
when operating in COS-mode. Single bits
in the PCD's can be filtered in/out.
Function:
Disables the built-in FTP server.
Enables the built-in FTP server.
Function:
Disables the build-in HTTP (web) server.
Enables the build-in HTTP (web) server.
Function:
Enables the SMTP (e-mail) service on the option.
Function:
ent socket channel. This enables FC-telegrams to
be sent transparently on Ethernet via TCP. Default
value is 4000, 0 means disabled.
MG.33.M9.02 - VLT
FC 300 Programming Guide
3.13.6 12-9* Advanced Ethernet Settings
12-90 Cable Diagnostics
Option:
[0]
Disable
*
[1]
Enable
NOTE
The cable diagnostics function will only be issued on
ports where there is no link (see par. 12-10, Link Status)
12-91 Auto Cross-Over
Option:
[0]
Disable
[1]
Enable
*
NOTE
Disabling of the auto cross-over function will require
crossed Ethernet cables for daisy-chaining the options.
12-92 IGMP Snooping
Option:
[0]
Disable Disables the IGMP snooping function.
[1]
Enable Enables the IGMP snooping function.
*
12-93 Cable Error Length
Option:
[0] Error length
Port 1 (0 –
200m)
[1] Error length
Port 2 (0 –
200m)
®
is a registered Danfoss trademark
Function:
Enables/disables advanced Cable diagnosis function.
If enabled, the distance to cable errors can be read
out in par. 12-93. The parameter resumes to the
default setting of Disable after the diagnostics have
finished.
Function:
Disables the auto cross-over function.
Enables the auto cross-over function.
Function:
This prevents flooding of the Ethernet protocol stack
by only forwarding multicast packets to ports that
are a member of the multicast group
Function:
If Cable Diagnostics is enabled in par. 12-90,
the built-in switch is able via Time Domain
Reflectometry (TDR). This is a measurement
technique which detects common cabling
problems such as open circuits, short circuits
and impedance mismatches or breaks in
transmission cables. The distance from the
option to the error is displayed in meters with
an accuracy of +/- 2m. The value 0 means no
errors detected.

Advertisement

Table of Contents
loading

Table of Contents