Danfoss FC 300 Programming Manual page 132

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
13-51 SL Controller Event
Array [20]
Option:
[85] Digital input x46/13
3
3
13-52 SL Controller Action
Array [20]
Option:
[0]
DISABLED
*
[1]
No action
[2]
Select set-up 1 Select set-up 1 [2] - changes the active set-up
[3]
Select set-up 2 Select set-up 2 [3] - changes the active set-up
[4]
Select set-up 3 Select set-up 3 [4] - changes the active set-up
[5]
Select set-up 4 Select set-up 4 [5] - changes the active set-up
[10] Select preset
ref 0
[11] Select preset
ref 1
[12] Select preset
ref 2
132
FC 300 Programming Guide
Function:
Function:
Select the action corresponding to the SLC
event. Actions are executed when the
corresponding event (defined in
par. 13-51 SL Controller Event) is evaluated as
true. The following actions are available for
selection:
*DISABLED [0]
No action [1]
(par. 0-10) to '1'.
If the set-up is changed, it will merge with
other set-up commands coming from either
the digital inputs or via a fieldbus.
(par. 0-10) to '2'.
If the set-up is changed, it will merge with
other set-up commands coming from either
the digital inputs or via a fieldbus.
(par. 0-10) to '3'.
If the set-up is changed, it will merge with
other set-up commands coming from either
the digital inputs or via a fieldbus.
(par. 0-10) to '4'.
If the set-up is changed, it will merge with
other set-up commands coming from either
the digital inputs or via a fieldbus.
Select preset reference 0 [10] – selects preset
reference 0.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
Select preset reference 1 [11] – selects preset
reference 1.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
Select preset reference 2 [12] – selects preset
reference 2.
If the active preset reference is changed, it
will merge with other preset reference
MG.33.M9.02 - VLT
13-52 SL Controller Action
Array [20]
Option:
Function:
commands coming from either the digital
inputs or via a fieldbus.
[13] Select preset
Select preset reference 3 [13] – selects preset
ref 3
reference 3.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[14] Select preset
Select preset reference 4 [14] – selects preset
ref 4
reference 4.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[15] Select preset
Select preset reference 5 [15] – selects preset
ref 5
reference 5.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[16] Select preset
Select preset reference 6 [16] – selects preset
ref 6
reference 6.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[17] Select preset
Select preset reference 7 [17] - selects preset
ref 7
reference 7.
If the active preset reference is changed, it
will merge with other preset reference
commands coming from either the digital
inputs or via a fieldbus.
[18] Select ramp 1
Select ramp 1 [18] - selects ramp 1.
[19] Select ramp 2
Select ramp 2 [19] - selects ramp 2.
[20] Select ramp 3
Select ramp 3 [20] - selects ramp 3.
[21] Select ramp 4
Select ramp 4 [21] - selects ramp 4.
[22] Run
Run [22] - issues a start command to the
frequency converter.
[23] Run reverse
Run reverse [23] - issues a start reverse
command to the frequency converter.
[24] Stop
Stop [24] - issues a stop command to the
frequency converter.
[25] Qstop
Qstop [25] - issues a quick stop command to
the frequency converter.
[26] Dcstop
Dcstop [26] - issues a DC stop command to
the frequency converter.
®
is a registered Danfoss trademark

Advertisement

Table of Contents
loading