Parameter Descriptions
6-50 Terminal 42 Output
Option:
Function:
[142] Bus ctrl
Par. 4-54 Warning Reference Low defines the
4-20mA
behaviour of the analog output in case of bus
t.o.
time-out.
[149] Torque %
Analogue output at zero torque = 12 mA.
lim
Motoric torque will increase the output current
4-20mA
to max torque limit 20 mA (set in
par. 4-16 Torque Limit Motor Mode).
Generative torque will decrease the output to
torque limit Generator Mode (set in
par. 4-17 Torque Limit Generator Mode)
Ex: par. 4-16 Torque Limit Motor Mode: 200% and
par. 4-17 Torque Limit Generator Mode: 200%. 20
mA = 200% Motoric and 4 mA = 200% Genera-
toric.
[150] Max Out
In relation to par. 4-19 Max Output Frequency.
Fr
4-20mA
6-51 Terminal 42 Output Min Scale
Range:
Function:
0.00 %
[0.00 -
Scale for the minimum output (0 or 4 mA)
*
200.00 %]
of the analogue signal at terminal 42.
Set the value to be the percentage of the
full range of the variable selected in
par. 6-50 Terminal 42 Output.
6-52 Terminal 42 Output Max Scale
Range:
Function:
100.00
[0.00 -
Scale the maximum output of the selected
%
200.00 %]
analog signal at terminal 42. Set the value to
*
the maximum value of the current signal
output. Scale the output to give a current
lower than 20 mA at full scale; or 20 mA at an
output below 100% of the maximum signal
value. If 20 mA is the desired output current
at a value between 0 - 100% of the full-scale
output, programme the percentage value in
the parameter, i.e. 50% = 20 mA. If a current
between 4 and 20 mA is desired at maximum
output (100%), calculate the percentage
value as follows:
20
mA
/
desired maximum current x
20
i
.
e
. 10
mA
:
x
100 = 200 %
10
FC 300 Programming Guide
6-53 Terminal 42 Output Bus Control
Range:
0.00 %
6-54 Terminal 42 Output Timeout Preset
Range:
0.00 %
6-55 Analog Output Filter
Option:
[0]
[1]
100 %
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
[0.00 - 100.00 %] Holds the level of Output 42 if
*
controlled by bus.
Function:
[0.00 -
Holds the preset level of Output 42.
*
100.00 %]
In case of a bus timeout and a timeout
function is selected in par. 6-50 Terminal
42 Output the output will preset to this
level.
Function:
The following readout analogue parameters from
selection in par. 6-50 Terminal 42 Output have a filter
selected when par. 6-55 Analog Output Filter is on:
Selection
Motor current (0 - I
)
max
Torque limit (0 - T
)
lim
Rated torque (0 - T
)
nom
Power (0 - P
)
nom
Speed (0 - Speedmax)
Off Filter off
*
On Filter on
3
0-20 mA
4-20 mA
[103]
[133]
[104]
[134]
[105]
[135]
[106]
[136]
[107]
[137]
89