3.13 Parameters: 12-** Ethernet

3.13.1 12-0* IP Settings
12-00 IP Address Assignment
3
3
Option:
[0]
Manual
*
[1]
DHCP
[2]
BOOTP
12-01 IP Address
Range:
[000.000.000.000 -
255.255.255.255]
12-02 Subnet Mask
Range:
[000.000.000.000 -
255.255.255.255]
12-03 Default Gateway
Range:
[000.000.000.000 –
255.255.255.255]
12-04 DHCP Server
Range:
[000.000.000.000 –
255.255.255.255]
NOTE
A power-cycle is necessary after setting the IP parame-
ters manually.
12-05 Lease Expires
Range:
[dd:hh:mm:ss] Read only. Displays the lease-time left for the
12-06 Name Servers
Option:
[0] Primary DNS
[1] Secondary DNS
12-07 Domain Name
Range:
Blank
[0-19 characters] Domain name of the attached network.
118
FC 300 Programming Guide
Function:
Selects the IP Address assignment method.
IP-address can be set in par. 12-01 IP Address.
IP-address is assigned via DHCP server.
IP-address is assigned via BOOTP server.
Function:
Configure the IP address of the
option. Read-only if par. 12-00 set to
DHCP or BOOTP.
Function:
Configure the IP subnet mask of the
option. Read-only if par. 12-00 set to
DHCP or BOOTP.
Function:
Configure the IP default gateway of
the option. Read-only if par. 12-00 set
to DHCP or BOOTP.
Function:
Read only. Displays the IP address
of the found DHCP or BOOTP server.
Function:
current DHCP-assigned IP address.
Function:
IP addresses of Domain Name Servers. Can be
automatically assigned when using DHCP.
Function:
Can be automatically assigned when
using DHCP.
MG.33.M9.02 - VLT
12-08 Host Name
Range:
Blank
[0-19 characters]
12-09 Physical Address
Range:
[00:1B:08:00:00:00 – 00:1B:
08:FF:FF:FF]
3.13.2 12-1* Ethernet Link Parameters
12-1* Ethernet Link Parameters
Option:
Function:
Applies for whole Par. group.
[0]
Port 1
[1]
Port 2
12-10 Link Status
Option:
Function:
Read only. Displays the link status of the Ethernet
ports.
[0] No link
[1] Link
12-11 Link Duration
Option:
Link Duration Port 1
(dd:hh:mm:ss)
12-12 Auto Negotiation
Option: Function:
Configures Auto Negotiation of Ethernet link parameters,
for each port: ON or OFF.
[0] Off Link Speed and Link Duplex can be configured in par. 12-13
and 12-14.
[1] On
12-13 Link Speed
Option:
Function:
Forces the link speed for each port in 10 or 100
Mbps. If par. 12-12 is set to: ON, this parameter is
read only and displays the actual link speed.
"None" is displayed if no link is present.
[0]
None
*
[1]
10 Mbps
[2]
100 Mbps
12-14 Link Duplex
Option:
Function:
Forces the duplex for each port to Full or Half
duplex. If par. 12-12 is set to: ON, this parameter
is read only.
[0]
Half duplex
[1]
Full duplex
*
®
is a registered Danfoss trademark
Function:
Logical (given) name of option.
Function:
Read only Displays the Physical
(MAC) address of the option.
Function:
Read only. Displays the duration of
the present link on each port in
dd:hh:mm:ss.