Danfoss FC 300 Programming Manual page 78

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113),
Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105),
Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
3
3
Option:
[40]
Out of ref range
[41]
Below reference,
low
[42]
Above ref, high
[43]
Extended PID Limit
[45]
Bus ctrl.
[46]
Bus ctrl, 1 if timeout Controls output via bus. The state of
[47]
Bus ctrl, 0 if timeout Controls output via bus. The state of
[51]
MCO controlled
[60]
Comparator 0
[61]
Comparator 1
[62]
Comparator 2
[63]
Comparator 3
78
FC 300 Programming Guide
Function:
par. 4-35 Tracking Error is larger than
selected the digital output/relay is
active.
Active when the actual speed is
outside settings in par. 4-52 Warning
Speed Low to par. 4-55 Warning
Reference High.
Active when actual speed is below
speed reference setting.
Active when actual speed is above
speed reference setting.
Controls digital output/relay via bus.
The state of the output is set in
par. 5-90 Digital & Relay Bus Control.
The output state is retained in the
event of bus time-out.
the output is set in par. 5-90 Digital &
Relay Bus Control. In the event of bus
time-out the output state is set high
(On).
the output is set in par. 5-90 Digital &
Relay Bus Control. In the event of bus
time-out the output state is set low
(Off).
Active when a MCO 302 or MCO 305 is
connected. The output is controlled
from option.
See par. group 13-1* (Smart Logic
Control). If Comparator 0 in SLC is
TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-1* (Smart Logic
Control). If Comparator 1 in SLC is
TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-1* (Smart Logic
Control). If Comparator 2 in SLC is
TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-1* (Smart Logic
Control). If Comparator 3 in SLC is
TRUE, the output will go high.
Otherwise, it will be low.
MG.33.M9.02 - VLT
5-40 Function Relay
Array [9]
(Relay 1 [0], Relay 2 [1], Relay 3 [2] (MCB 113), Relay 4 [3] (MCB 113),
Relay 5 [4] (MCB 113), Relay 6 [5] (MCB 113), Relay 7 [6] (MCB 105),
Relay 8 [7] (MCB 105), Relay 9 [8] (MCB 105))
Option:
[64]
Comparator 4
[65]
Comparator 5
[70]
Logic rule 0
[71]
Logic rule 1
[72]
Logic rule 2
[73]
Logic rule 3
[74]
Logic rule 4
[75]
Logic rule 5
[80]
SL digital output A
[81]
SL digital output B
[82]
SL digital output C
[83]
SL digital output D
®
is a registered Danfoss trademark
Function:
See par. group 13-1* (Smart Logic
Control). If Comparator 4 in SLC is
TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-1* (Smart Logic
Control). If Comparator 5 in SLC is
TRUE, the output will go high.
Otherwise, it will be low.
See par. group 13-4*(Smart Logic
Control). If Logic Rule 0 in SLC is TRUE,
the output will go high. Otherwise, it
will be low.
See par. group 13-4*(Smart Logic
Control). If Logic Rule 1 in SLC is TRUE,
the output will go high. Otherwise, it
will be low.
See par. group 13-4*(Smart Logic
Control). If Logic Rule 2 in SLC is TRUE,
the output will go high. Otherwise, it
will be low.
See par. group 13-4*(Smart Logic
Control). If Logic Rule 3 in SLC is TRUE,
the output will go high. Otherwise, it
will be low.
See par. group 13-4*(Smart Logic
Control). If Logic Rule 4 in SLC is TRUE,
the output will go high. Otherwise, it
will be low.
See par. group 13-4*(Smart Logic
Control). If Logic Rule 5 in SLC is TRUE,
the output will go high. Otherwise, it
will be low.
See par. 13-52 SL Controller Action.
Output A is low on Smart Logic Action
[32]. Output A is high on Smart Logic
Action [38].
See par. 13-52 SL Controller Action.
Output B is low on Smart Logic Action
[33]. Output B is high on Smart Logic
Action [39].
See par. 13-52 SL Controller Action.
Output C is low on Smart Logic Action
[34]. Output C is high on Smart Logic
Action [40].
See par. 13-52 SL Controller Action.
Output D is low on Smart Logic Action

Advertisement

Table of Contents
loading

Table of Contents