Parameters: 35-** Sensor Input Option - Danfoss FC 300 Programming Manual

Hide thumbs Also See for FC 300:
Table of Contents

Advertisement

Parameter Descriptions
3.21 Parameters: 35-** Sensor Input
Option
3.21.1 35-0* Temp. Input Mode (MCB 114)
35-00 Term. X48/4 Temp. Unit
Select the unit to be used with temperature input X48/4 settings
and readouts:
Option:
[60]
°C
*
[160]
°F
35-01 Term. X48/4 Input Type
View the temperature sensor type detected at input X48/4:
Option:
[0]
Not Connected
*
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-02 Term. X48/7 Temp. Unit
Select the unit to be used with temperature input X48/7 settings
and readouts:
Option:
[60]
°C
*
[160]
°F
35-03 Term. X48/7 Input Type
View the temperature sensor type detected at input X48/7:
Option:
[0]
Not Connected
*
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
35-04 Term. X48/10 Temp. Unit
Select the unit to be used with temperature input X48/10 settings
and readouts:
Option:
[60]
°C
*
[160]
°F
35-05 Term. X48/10 Input Type
View the temperature sensor type detected at input X48/10:
Option:
[0]
Not Connected
*
[1]
PT100 2-wire
[3]
PT1000 2-wire
[5]
PT100 3-wire
[7]
PT1000 3-wire
FC 300 Programming Guide
35-06 Temperature Sensor Alarm Function
Select the alarm function:
Option:
[0]
[2]
[5]
3.21.2 35-1* Temp. Input X48/4 (MCB 114)
Function:
35-14 Term. X48/4 Filter Time Constant
Range:
0.001 s
Function:
35-15 Term. X48/4 Temp. Monitor
This parameter gives the possibility of enabling or disabling the
temperature monitor for terminal X48/4. The temperature limits
can be set in par. 35-16 and par. 35-17.
Option:
[0]
[1]
Function:
35-16 Term. X48/4 Low Temp. Limit
Range:
Application
dependent
Function:
35-17 Term. X48/4 High Temp. Limit
Range:
Application
dependent
Function:
3.21.3 35-2* Temp. Input X48/7 (MCB 114)
35-24 Term. X48/7 Filter Time Constant
Range:
0.001 s
Function:
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Off
Stop
Stop and trip
*
Function:
[0.001 -
Enter the filter time constant. This is a first-
*
10.000 s]
order digital low pass filter time constant
for suppressing electrical noise in terminal
X48/4. A high time constant value
improves dampening but also increases
the time delay through the filter.
Disabled
*
Enabled
[Application
dependant]
*
[Application
dependant]
*
Function:
[0.001 -
Enter the filter time constant. This is a first-
*
10.000 s]
order digital low pass filter time constant
for suppressing electrical noise in terminal
X48/7. A high time constant value
improves dampening but also increases
the time delay through the filter.
Function:
Function:
Function:
Enter the minimum tempera-
ture reading that is expected
for normal operation of the
temperature sensor at terminal
X48/4.
Function:
Enter the maximum tempera-
ture reading that is expected
for normal operation of the
temperature sensor at terminal
X48/4.