Parameter Descriptions
6-13 Terminal 53 High Current
Range:
20.00 mA
[Application
*
dependant]
3
3
6-14 Terminal 53 Low Ref./Feedb. Value
Range:
0.000 N/
[-999999.999 -
A
999999.999 N/A]
*
6-15 Terminal 53 High Ref./Feedb. Value
Range:
Application
dependent
*
6-16 Terminal 53 Filter Time Constant
Range:
0.001 s
[0.001 -
*
10.000 s]
3.8.3 6-2* Analog Input 2
Parameters for configuring the scaling and limits for analog
input 2 (terminal 54).
6-20 Terminal 54 Low Voltage
Range:
0.07 V
[Application
*
dependant]
86
Function:
Enter the high current value
corresponding to the high reference/
feedback set in par. 6-15 Terminal 53
High Ref./Feedb. Value.
Function:
Enter the analog input scaling
value that corresponds to the low
voltage/low current set in
par. 6-10 Terminal 53 Low Voltage
and par. 6-12 Terminal 53 Low
Current.
Function:
[-999999.999 -
Enter the analog input scaling
999999.999
value that corresponds to the
ReferenceFeed-
maximum reference feedback
backUnit]
value set in par. 6-11 Terminal 53
High Voltage and
par. 6-13 Terminal 53 High
Current.
Function:
Enter the time constant. This is a first-order
digital low pass filter time constant for
suppressing electrical noise in terminal 53.
A high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.
Function:
Enter the low voltage value. This analog
input scaling value should correspond to
the minimum reference value, set in
par. 3-02 Minimum Reference. See also the
section Reference Handling.
MG.33.M9.02 - VLT
FC 300 Programming Guide
6-21 Terminal 54 High Voltage
Range:
10.00 V
*
6-22 Terminal 54 Low Current
Range:
0.14
mA
*
6-23 Terminal 54 High Current
Range:
20.00 mA
*
6-24 Terminal 54 Low Ref./Feedb. Value
Range:
0 Reference-
FeedbackUnit
6-25 Terminal 54 High Ref./Feedb. Value
Range:
Application
dependent
6-26 Terminal 54 Filter Time Constant
Range:
0.001 s
*
®
is a registered Danfoss trademark
Function:
[Application
Enter the high voltage value. This
dependant]
analog input scaling value should
correspond to the high reference/
feedback value set in par. 6-25 Terminal
54 High Ref./Feedb. Value.
Function:
[Application
Enter the low current value. This reference
dependant]
signal should correspond to the minimum
reference value, set in par. 3-02 Minimum
Reference. The value must be set at >2 mA
in order to activate the Live Zero Time-out
Function in par. 6-01 Live Zero Timeout
Function.
Function:
[Application
Enter the high current value
dependant]
corresponding to the high reference/
feedback value set in
par. 6-25 Terminal 54 High Ref./Feedb.
Value.
Function:
[-999999.999 -
Enter the analog input scaling
999999.999
value that corresponds to the
*
ReferenceFeed-
minimum reference feedback
backUnit]
value set in par. 3-02 Minimum
Reference.
Function:
[-999999.999 -
Enter the analog input scaling
999999.999
value that corresponds to the
*
ReferenceFeed-
maximum reference feedback
backUnit]
value set in par. 3-03 Maximum
Reference.
Function:
[0.001 -
Enter the time constant. This is a first-order
10.000 s]
digital low pass filter time constant for
suppressing electrical noise in terminal 54.
A high time constant value improves
dampening but also increases the time
delay through the filter.
This parameter cannot be adjusted while
the motor is running.