Parameter Descriptions
1-04 Overload Mode
Option:
Function:
[0]
High torque
Allows up to 160% over torque.
*
[1]
Normal torque For oversized motor - allows up to 110% over
torque.
This parameter cannot be adjusted while the motor is running.
1-05 Local Mode Configuration
Option:
Function:
Select which application configuration mode
(par. 1-00 Configuration Mode), i.e. application
control principle, to use when a Local (LCP)
Reference is active. A Local Reference can be
active only when par. 3-13 Reference Site is set
to [0] or [2]. By default the local reference is
active in Hand Mode only.
[0]
Speed open
loop
[1]
Speed closed
loop
[2]
As mode par
*
1-00
1-06 Clockwise Direction
This parameter defines the term "Clockwise" corresponding to the
LCP direction arrow. Used for easy change of direction of shaft
rotation without swapping motor wires. (Valid from SW version
5.84)
Option:
[0]
Normal
*
[1]
Inverse
This parameter cannot be changed while the motor is running.
FC 300 Programming Guide
Function:
Motor shaft will turn in clockwise
direction when frequency convert-
er is connected U -> U; V -> V, and
W -> W to motor.
Motor shaft will turn in counter
clockwise direction when frequen-
cy converter is connected U -> U; V
-> V, and W -> W to motor.
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
3.3.2 1-1* Motor Selection
This par. group cannot be adjusted while the motor is running.
1-10 Motor Construction
Option:
Function:
Select the motor construction type.
[0]
Asynchron
For asynchronous motors.
*
[1]
PM, non salient
For permanent magnet (PM) motors.
SPM
Note that PM motors are divided into two
groups, with either surface mounted (non
salient) or interior (salient) magnets.
Motor construction can either be asynchronous or permanent
magnet (PM) motor.
3.3.3 1-2* Motor Data
Par. group 1-2* comprises input data from the nameplate on
the connected motor.
NOTE
Changing the value of these parameters affects the
setting of other parameters.
1-20 Motor Power [kW]
Range:
Function:
Applica-
[Applica-
Enter the nominal motor power in kW
tion
tion
according to the motor nameplate data.
depend-
dependant]
The default value corresponds to the
ent
nominal rated output of the unit.
*
This parameter cannot be adjusted while
the motor is running. This parameter is
visible in LCP if par. 0-03 Regional
Settings is International [0].
NOTE
Four sizes down, one size up
from nominal unit rating.
1-21 Motor Power [HP]
Range:
Function:
Application
[Applica-
Enter the nominal motor power in HP
dependent
tion
according to the motor nameplate
*
dependant]
data. The default value corresponds to
the nominal rated output of the unit.
This parameter is visible in LCP if
par. 0-03 Regional Settings is US [1]
3
3
35