Parameter Descriptions
0-20 Display Line 1.1 Small
Option:
[1639]
Control Card
Temp.
[1650]
External Reference Sum of the external reference as a
3
3
[1651]
Pulse Reference
[1652]
Feedback [Unit]
[1653]
Digi Pot Reference
[1657]
Feedback [RPM]
[1660]
Digital Input
[1661]
Terminal 53
Switch Setting
[1662]
Analog Input 53
[1663]
Terminal 54
Switch Setting
[1664]
Analog Input 54
[1665]
Analog Output 42
[mA]
[1666]
Digital Output
[bin]
[1667]
Freq. Input #29
[Hz]
[1668]
Freq. Input #33
[Hz]
[1669]
Pulse Output #27
[Hz]
[1670]
Pulse Output #29
[Hz]
[1671]
Relay Output [bin]
[1672]
Counter A
[1673]
Counter B
[1674]
Prec. Stop Counter Display the actual counter value.
[1675]
Analog In X30/11
28
FC 300 Programming Guide
Function:
Temperature of the control card.
percentage, i.e. the sum of analog/
pulse/bus.
Frequency in Hz connected to the
digital inputs (18, 19 or 32, 33).
Reference value from programmed
digital input(s).
Signal states form the 6 digital
terminals (18, 19, 27, 29, 32 and 33).
There are 16 bits in total, but only six
of them are used. Input 18
corresponds to the leftmost of the
used bits. Signal low = 0; Signal high
= 1.
Setting of input terminal 54. Current
= 0; Voltage = 1.
Actual value at input 53 either as a
reference or protection value.
Setting of input terminal 54. Current
= 0; Voltage = 1.
Actual value at input 54 either as
reference or protection value.
Actual value at output 42 in mA. Use
par. 6-50 Terminal 42 Output to select
the value to be shown.
Binary value of all digital outputs.
Actual value of the frequency applied
at terminal 29 as an impulse input.
Actual value of the frequency applied
at terminal 33 as an impulse input.
Actual value of impulses applied to
terminal 27 in digital output mode.
Actual value of impulses applied to
terminal 29 in digital output mode.
Application dependent (e.g. SLC
Control)
Application dependent (e.g. SLC
Control)
Actual value at input X30/11 either as
reference or protection value.
®
MG.33.M9.02 - VLT
0-20 Display Line 1.1 Small
Option:
[1676]
Analog In X30/12
[1677]
Analog Out X30/8
[mA]
[1678]
Analog Out X45/1
[mA]
[1679]
Analog Out X45/3
[mA]
[1680]
Fieldbus CTW 1
[1682]
Fieldbus REF 1
[1684]
Comm. Option
STW
[1685]
FC Port CTW 1
[1686]
FC Port REF 1
[1690]
Alarm Word
[1691]
Alarm Word 2
[1692]
Warning Word
[1693]
Warning Word 2
[1694]
Ext. Status Word
[1836]
Analog Input
X48/2 [mA]
[1837]
Temp. Input X48/4
[1838]
Temp. Input X48/7
[1839]
Temp. Input
X48/10
[1860]
Digital Input 2
[1890]
Process PID Error
[1891]
Process PID
Output
[1892]
Process PID
Clamped Output
[1893]
Process PID Gain
Scaled Output
[3019]
Wobble Delta
Freq. Scaled
[3110]
Bypass Status
Word
[3111]
Bypass Running
Hours
[3401]
PCD 1 Write to
MCO
[3402]
PCD 2 Write to
MCO
is a registered Danfoss trademark
Function:
Actual value at input X30/12 either as
reference or protection value.
Actual value at output X30/8 in mA.
Use par. 6-60 Terminal X30/8 Output
to select the value to be shown.
Control word (CTW) received from
the Bus Master.
Main reference value sent with
control word from the Bus Master.
Extended fieldbus communication
option status word.
Control word (CTW) received from
the Bus Master.
Status word (STW) sent to the Bus
Master.
One or more alarms in a Hex code.
One or more alarms in a Hex code.
One or more warnings in a Hex code.
One or more warnings in a Hex code.
One or more status conditions in a
Hex code.