Parameter Descriptions
5-13 Terminal 29 Digital Input
Option:
Function:
Select the function from the available digital input
range and the additional options [60], [61], [63] and
[64]. Counters are used in Smart Logic Control
functions.This parameter is available for FC 302 only.
[14]
Jog Functions are described under 5-1* Digital Inputs
*
5-14 Terminal 32 Digital Input
Option:
Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in Smart
Logic Control functions.
[0]
No operation Functions are described under 5-1* Digital
*
Inputs
5-15 Terminal 33 Digital Input
Option:
Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in Smart
Logic Control functions.
[0]
No operation Functions are described under 5-1* Digital
*
Inputs
5-16 Terminal X30/2 Digital Input
Option:
Function:
[0]
No operation This parameter is active when option module
*
MCB101 is installed in the frequency convert-
er. Functions are described under 5-1* Digital
Inputs
5-17 Terminal X30/3 Digital Input
Option:
Function:
[0]
No operation This parameter is active when option module
*
MCB101 is installed in the frequency convert-
er. Functions are described under 5-1* Digital
Inputs
5-18 Terminal X30/4 Digital Input
Option:
Function:
[0]
No operation This parameter is active when option module
*
MCB101 is installed in the frequency convert-
er. Functions are described under 5-1* Digital
Inputs
5-19 Terminal 37 Safe Stop
Option:
Function:
[1]
Safe Stop
Coasts frequency converter when safe stop is
*
Alarm
activated. Manual reset from LCP, digital input
or fieldbus.
[3]
Safe Stop
Coasts frequency converter when safe stop is
Warning
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset.
FC 300 Programming Guide
5-19 Terminal 37 Safe Stop
Option:
[4]
[5]
[6]
[7]
[8]
[9]
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor Card is connected.
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
PTC 1 Alarm Coasts frequency converter when safe stop is
activated. Manual reset from LCP, digital input
or fieldbus. Choice 4 is only available when the
MCB 112 PTC Thermistor Card is connected.
PTC 1
Coasts frequency converter when safe stop is
Warning
activated (T-37 off). When safe stop circuit is
reestablished, the frequency converter will
continue without manual reset, unless a Digital
Input set to PTC Card 1 [80] is still enabled.
Choice 5 is only available when the MCB 112
PTC Thermistor Card is connected.
PTC 1 &
This choice is used when the PTC option is
Relay A
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency converter
when safe stop is activated. Manual reset from
LCP, digital input or fieldbus. Choice 6 is only
available when the MCB 112 PTC Thermistor
Card is connected.
PTC 1 &
This choice is used when the PTC option is
Relay W
gated together with a Stop button through a
Safety relay to T-37. Coasts frequency converter
when safe stop is activated (T-37 off). When safe
stop circuit is reestablished, the frequency
converter will continue without manual reset,
unless a Digital Input set to PTC Card 1 [80] is
(still) enabled. Choice 7 is only available when
the MCB 112 PTC Thermistor Card is connected.
PTC 1 &
This choice makes it possible to use a combina-
Relay A/W
tion of Alarm and Warning. Choice 8 is only
available when the MCB 112 PTC Thermistor
Card is connected.
PTC 1 &
This choice makes it possible to use a combina-
Relay W/A
tion of Alarm and Warning. Choice 9 is only
available when the MCB 112 PTC Thermistor
Card is connected.
3
3
71