Parameter Descriptions
8-56 Preset Reference Select
Option:
Function:
Select control of the frequency converter Preset
Reference selection via the terminals (digital
input) and/or via the fieldbus.
[0]
Digital
Activates Preset Reference selection via a digital
input
input.
[1]
Bus
Activates Preset Reference selection via the
serial communication port or fieldbus option.
[2]
Logic AND
Activates Preset Reference selection via the
fieldbus/serial communication port, AND
additionally via one of the digital inputs.
[3]
Logic OR
Activates the Preset Reference selection via the
*
fieldbus/serial communication port OR via one
of the digital inputs.
8-57 Profidrive OFF2 Select
Select control of the drive OFF2 selection via the terminals (digital
input) and/or via the fieldbus. This parameter is active only when
par. 8-01 Control Site is set to [0] Digital and ctrl. word and par.
8-10 is set to [1] Profidrive profile.
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
8-58 Profidrive OFF3 Select
Select control of the drive OFF3 selection via the terminals (digital
input) and/or via the fieldbus. This parameter is active only when
par. 8-01 Control Site is set to [0] Digital and control word and par.
8-10 is set to [1] Profidrive profile.
Option:
[0]
Digital input
[1]
Bus
[2]
Logic AND
[3]
Logic OR
*
FC 300 Programming Guide
3.10.6 8-8* FC Port Diagnostics
These parameters are used for monitoring the Bus communi-
cation via the Port.
8-80 Bus Message Count
Range:
0 N/A
8-81 Bus Error Count
Range:
0 N/A
8-82 Slave Messages Rcvd
Range:
0 N/A
8-83 Slave Error Count
Function:
Range:
0 N/A
3.10.7 8-9* Bus Jog
8-90 Bus Jog 1 Speed
Range:
100 RPM
Function:
8-91 Bus Jog 2 Speed
Range:
200 RPM
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
Function:
[0 - 0 N/A] This parameter shows the number of valid
*
telegrams detected on the bus.
Function:
[0 - 0 N/A] This parameter shows the number of
*
telegrams with faults (e.g. CRC fault),
detected on the bus.
Function:
[0 - 0 N/A] This parameter shows the number of valid
*
telegrams addressed to the slave, sent by the
frequency converter.
Function:
[0 - 0 N/A] This parameter shows the number of error
*
telegrams, which could not be executed by
the frequency converter.
Function:
[Application
Enter the jog speed. This is a fixed
*
dependant]
jog speed activated via the serial
port or fieldbus option.
Function:
[Application
Enter the jog speed. This is a fixed
*
dependant]
jog speed activated via the serial
port or fieldbus option.
3
3
107