Parameter Descriptions
16-52 Feedback [Unit]
Range:
0.000
[-999999.999 -
Reference-
999999.999
FeedbackU-
ReferenceFeed-
nit
backUnit]
*
16-53 Digi Pot Reference
Range:
Function:
0.00
[-200.00 - 200.00 ] View the contribution of the Digital
*
Potentiometer to the actual reference.
16-57 Feedback [RPM]
Range:
Function:
0 RPM
[-30000 -
Read-out parameter where the actual
*
30000 RPM]
motor RPM from the feed-back source can
be read in both closed loop and open
loop. The feed-back source is selected by
par. 7-00.
3.17.5 16-6* Inputs and Outputs
16-60 Digital Input
Range:
Function:
0
[0 -
View the signal states from the active digital inputs.
N/
1023
Example: Input 18 corresponds to bit no. 5, '0' = no
A
N/A]
signal, '1' = connected signal. Bit 6 works in the
*
opposite way, on = '0', off = '1' (safe stop input).
Bit 0
Digital input term. 33
Bit 1
Digital input term. 32
Bit 2
Digital input term. 29
Bit 3
Digital input term. 27
Bit 4
Digital input term. 19
Bit 5
Digital input term. 18
Bit 6
Digital input term. 37
Bit 7
Digital input GP I/O term. X30/4
Bit 8
Digital input GP I/O term. X30/3
Bit 9
Digital input GP I/O term. X30/2
Bit 10-63
Reserved for future terminals
FC 300 Programming Guide
Function:
View the feedback unit resulting
from the selection of unit and
scaling in par. 3-00 Reference
Range, par. 3-01 Reference/
Feedback Unit, par. 3-02 Minimum
Reference and par. 3-03 Maximum
Reference.
®
MG.33.M9.02 - VLT
is a registered Danfoss trademark
16-60 Digital Input
Range:
Function:
16-61 Terminal 53 Switch Setting
Option:
Function:
View the setting of input terminal 53. Current =
0; Voltage = 1.
[0]
Current
*
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-62 Analog Input 53
Range:
Function:
0.000
[-20.000 - 20.000 ]
View the actual value at input 53.
*
16-63 Terminal 54 Switch Setting
Option:
Function:
View the setting of input terminal 54. Current =
0; Voltage = 1.
[0]
Current
*
[1]
Voltage
[2]
Pt 1000 [°C]
[3]
Pt 1000 [°F]
[4]
Ni 1000 [°C]
[5]
Ni 1000 [°F]
16-64 Analog Input 54
Range:
Function:
0.000
[-20.000 - 20.000 ]
View the actual value at input 54.
*
16-65 Analog Output 42 [mA]
Range:
Function:
0.000
[0.000 -
View the actual value at output 42 in mA.
*
30.000 ]
The value shown reflects the selection in
par. 6-50 Terminal 42 Output.
3
3